English

6. Manual Reset of Flow switch alarm Er01

Instructions are provided below on how to restart the unit operation after the intervention of flow
alarm "Er01".
In case of flow alarm, "Er01" will be shown on the unit display and
pump operation will be stopped
7. Manual Reset of Antifreeze alarm Er09 (only for EB2.0 Oil P
units)
Instructions are provided below on how to restart the unit operation after the intervention of antifreeze
alarm "Er09" with stopped pump, this occurs if antifreeze alarm persists for 30 seconds.
In case of antifreeze alarm persists for 30 seconds, "Er09" will be
shown on the unit display and pump operation will be stopped
10
Press "esc" button for 5 seconds to reset
the flow alarm and restart pump operation
Press "esc" button for 3 seconds to reset
the antifreeze alarm and restart pump operation