Alfa Laval Micro
Installation, service and operating instruction
12.2.2
CM737-Category 2: System Settings
Parameter
Para
meter
N:o
Summer heating in
1:SH
OTC mode
Economy function
2:SL
Economy function
3:Pd
12.2.3
CM737-Category 3: Boiler Settings
Parameter
Para
meter
N:o
Maximum central
1:CH
heating set point 2)
DHW set point 2)
2:HS
Supply water
3:St
temperature 3)
Return water
4:rt
temperature 3)
DHW temperature
5:Ht
3)
Outside
6:Ot
temperature 4)
Water pressure 3)
7:Pr
DHW storage
8:HO
overnight
DHW storage
9:HH
during HOLIDAY
Low capacity
10:LD
control
All manuals and user guides at all-guides.com
Factory Default Setting
Display
Description
0
Summer heating
disabled
20
The outside
temperature at which
the heating will switch
off
10
Diff between outside
and calculated water
supply temperature
Factory Default Setting
Display
Description
90
90°C or obtained from
the boiler
55
55°C or obtained from
the boiler
Actual
Temperature obtained
temp
from the boiler
(between 0°C and
99°C)
Actual
Temperature obtained
temp
from the boiler
Actual
Temperature obtained
temp
from the boiler
Actual
Between -30°C and
temp
99°C
Actual
Between 0.0 bar and
press
4.0 bar
1
DHW storage enabled
after last period of day
0
DHW storage
disabled during
HOLIDAY
1
Not applicable
38
Optional Setting
Display
Description
1 to 40
Minimum set point for the
heating and the pump will be
held on.
10 to 30
The economy function will be
disabled if the setting for
summer heating is not 0
If the calculated water
supply temperature is not
greater than the outside
temperature by this amount
the heating will switch off.
Optional Setting
Display
Description
40 to 90
40°C to 90°C adjustment in
1°C steps
40 to 80
40°C to 80°C adjustment in
1°C steps
N/A
Not applicable
N/A
Not applicable
N/A
Not applicable
N/A
Not applicable
N/A
Not applicable
0
DHW storage disabled after
last period of day
1
DHW storage enabled during
HOLIDAY
0
Not applicable