Télécharger Imprimer la page

S&P AIRSENS WIFI IAQ Mode D'emploi page 19

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 21
Fig. 2: Operating modes
MF1: Relay + Connec-
tair (reading)
Adjustable relay via P1
potentiometer
MF2: 0-10Vdc output
+ Connectair (reading)
Adjustable α angle via
P1 potentiometer
MF3: 2 -10Vdc output
+ Connectair (reading)
Adjustable α angle via
P1 potentiometer
MF4: Connectair control
Access to all operating modes and parameters via Connectair.
Note: If other switch combination is chosen, LED diffuser is switched off and digital/analo-
gue signals are inoperative.
Relay
1200ppm
Output
10V
α
0V
450ppm
800ppm
45% RH
60% RH
18ºC
20ºC
Output
10V
α
2V
450 ppm
800 ppm
45% RH
60% RH
18ºC
20ºC
Hysteresis
200ppm
5% RH
1ºC
2000ppm
Setpoint
70% RH
100% RH
30ºC
50ºC
2000ppm
Input
100% RH
50ºC
2000 ppm
Input
100% RH
50ºC
19