Electric connection: All cables used must fulfil with IEC 60.227.
5 x terminals, supply and relay ............ Min. 0,5 mm
2 x terminals, analogue output ............ Min. 0,25 mm
Note: Same tool can be used for both terminals types
Measurement range:
CO2 ....................................................... 450-2000ppm
VOC ....................................................... 450-2000ppm (CO2 equivalent relative)
RH......................................................... 45-100%
TEMP .................................................... 18-50ºC
Accuracy:
CO2 ....................................................... ± 50ppm
VOC ....................................................... ± 100ppm
RH......................................................... ± 2%
T............................................................ ± 0,4°C
Warm-up time:
CO2 ....................................................... 1 minute
VOC ....................................................... 5 minutes (relative reference)
RH/T ..................................................... 30 seconds
Ambient air humidity ........................... 10-95% without condensation
Case dimensions [height x width x deep.] .. 89 x 122 x 26 mm
ENVIRONMENTAL DATA
Ambient temperature .......................... 0-50°C
Covering classification ......................... IP30
Pollution degree................................... 2
Weight .................................................. 150 g
MAINTENANCE
Disconnect from supply before removing. Prevent the possibility of anyone else
connecting it while it is being inspected. Regular inspection of the appliance is
required, the frequency must be depend of the working conditions to avoid the
accumulation of dirt that could trigger risks and would reduce the life expectan-
cy. In all maintenance work, safety regulations in each country must be taken
into account.
cable / Máx. 1,5 mm² cable
2
M3 screw and 0,5 Nm torque
cable / Máx. 1,0 mm² cable
2
M2 screw and 0,3 Nm torque
EN
17