5.3. External protections
It is equipped with a connector that can be connected to various types of external mechanical protections, such as flow switches,
pressure switches, thermostats, etc.
The ESS connectors are used to wire these protections. The external protection devices are powered from the heat pump
connector at 24Vac.
5.4. Outside temperature probe
The outside temperature probe, supplied with the heat pump, has to be installed for the heat pump to work properly. Follow the
instructions below to install it.
Install the outside probe in a well ventilated area, but protected from wind and rain.
Do not install the outside probe at a distance of less than 1 m from windows or doors to avoid the effect of possible
currents of warm air.
Use a shielded 2-pole cable to prevent interferences.
Description
Outside temperature probe
5.5. External storage systems
These can be used to control DHW storage, heating and cooling temperatures using temperature probes.
Description
DHW inter-accumulator
Heating buffer storage tank
Cooling buffer storage tank
5.6. External production equipment
These are used to control production equipment handling of the various services, such as bypass valves or circulatory pumps.
All manuals and user guides at all-guides.com
Sgn
Com
Figure 1.1. Connection scheme of the external protection devices.
Analogue input
Table 1.1. Outside temperature probe connection terminals.
Analogue input
Analogue input
Analogue input
Table 1.2. Connection terminals for outlet units.
Installer manual ecoGEO HP
Signal
Type
NTC 10K 25ºC Probe
Signal
Type
NTC 10K 25ºC Probe
NTC 10K 25ºC Probe
NTC 10K 25ºC Probe
43
Connector
AI20
Connector
AI11
AI17
AI18