G
®
RHEASGARD
KLGF xx ⁄ RHEASREG
Schematic diagram
thershold
sb
offset
rel.
sb
LEDs
Plug for
display
12 11 13
NC M NO
Relay
SET-Potentiometer
thershold = switching point (min. 0.1m/s ... max. 20 m/s
Connecting diagram
sb
= start bridging (min. 0 s ... max. 120 s)
offset
= temperature (± 5K)
1
+UB 24V AC/DC
LEDs
(on = active)
2
Output 0-10 V Flow velocity
rel.
= relay / switching point exceeded
3
free
sb
= start bridging
–UB GND
4
Pushbutton
zero ⁄ set:
Hold down for 2 s → activate menu on display
Connecting diagram
Hold down for 10 s → set zero (0 m ⁄ s)
(sb LED flashes during process and turns off
when zero is set)
1
+UB 24V AC/DC
up ⁄ down (display versions):
2
free
When the menu is activated (2 s hold down of zero ⁄
free
3
set button), you can change between 'Flow' (flow speed)
4
–UB GND
and 'Vol' (volume rate). When 'Vol' is selected
→ enter surface area in cm² (up/down)
NC Normally Closed
12
→ zero ⁄ set button
11
M Common
→ enter unit (up ⁄ down)
13
NO Normally Open
→ zero ⁄ set button
Connecting diagram
1
+UB 24V AC/DC
2
Output 0-10 V / 4...20mA Flow velocity
Output 0-10 V / 4...20mA Temperature
3
4
–UB GND
NC Normally Closed
12
M Common
11
13
NO Normally Open
*
KLGFVT-W LCD:
Switching from flow measurand
to the alternative volume flow parameter
is menu-controlled on the display.
®
KLSW xx
KLGF /KLSW-x x LCD
KLGFT-W / KLGFVT-W LCD
Pushbutton
zero
set
1
2
3 4
+UB
OUT1
OUT2 GND
KLGF-U LCD
(display versions)
KLSW-W24 LCD
KLGFVT-W LCD
KLGFT-W
NC M NO
Relay
SET-Potentiometer
thershold = switching point (min. 0.1m/s ... max. 20 m/s
sb
= start bridging (min. 0 s ... max. 120 s)
offset
= temperature (± 5K)
LEDs
(on = active)
rel.
= relay / switching point exceeded
sb
= start bridging
Pushbutton
zero ⁄ set:
Hold down for 2 s → activate menu on display
Hold down for 10 s → set zero (0 m ⁄ s)
(sb LED flashes during process and turns off
when zero is set)
up ⁄ down (display versions):
When the menu is activated (2 s hold down of zero ⁄
set button), you can change between 'Flow' (flow speed)
and 'Vol' (volume rate). When 'Vol' is selected
→ enter surface area in cm² (up/down)
→ zero ⁄ set button
→ enter unit (up ⁄ down)
→ zero ⁄ set button
13
+UB
OUT1
OUT2 GND
Rev. Data - V35
(display versions)