In-duct fire damper BAE
PREPARATION FOR INSTALLATION
Fig. 1 Installation of end switch BA-S (accessories)
Pos. 1
Insert the holder in the T­slot in the inner ring of the shutter element
Pos. 2
Push the holder down to the stop in the T­slot
Pos. 3/4 Clip BA­S end switch to the holder. Then test the function of the push button.
Pos. 1
Holder
Fig. 2 Replace fusible link
Pos. 1
Press to the side of the fused link against the insert lever and remove
Pos. 2
Place the replacement fusible link (Accessories, Ref. no. 84974) in the fusible link holder and lock in place
Pos. 1
Fig. 2 Attach fusible link
Pos. 3
In order to attach fusible link, bend the catch springs in the inner ring of the shutter element outwards
Pos. 4
Push the two semicircular damper blades together so that the fusible link can be attached to the locking catch.
ACCESSORIES
End switch BA-S (kit)
with holder
Ref. no. 02585
End switch for BAE monitoring
and signalling of operating status
to the central building manage­
ment system. Attachable to all
standard diameters.
Replacement fusible link for BAE
Pos. 2
Pos. 2
Fusible link
Ref. no. 84974
Pos. 3
Pos. 3
Catch spring
Mounting sleeve EH (accessories)
Ref. no. see table
Mounting Ref.
Dimensions in mm
sleeve
no.
ø C ø D
EH 100
2639
101
EH 125
2640
128 123
EH 160
2641
162 158
EH 200
2642
201 197
2
Pos. 4
Pos. 4
ø E
ø F
98
92
120
92
120
114 140
120 150
Dimensions in mm
see table