1 Set-up/Connections/Installation
1.1 General operation of Bullerjan cook stoves
The Bullerjan cook stoves may only be operated with
closed fire room door.
Important! The stove may not be structurally modified in
any way. Only those spare parts may be installed which
are permitted by Bullerjan GmbH. If the stove is
structurally modified or is equipped with non-permitted
spare parts, any liability and warranty claims become
invalid.
1.2 Set-up
1.2.1 General Requirements
When installing the cook stoves and when connecting
them to exhaust gas systems, the relevant regulations
under public law, particularly the provisions of state
construction ordinances and the approved firing
regulations are to be followed.
The flue gas connection of the cook is placed on the
topplate of the stove. The diametre is 13 cm.
1.2.2 Combustion air supply
The room in which the stove is to be installed should at
least have a minimum volume of 4 m
heating capacity.
cook
per kW of nominal
3
1.2.3 Safety distance to combustible components
and furniture
Bullerjan cook: Distances to combustible components
cook
Front:
80 cm
Sides:
40 cm
Rear:
40 cm
1.2.3 Spark protection / protection of the floor
If the stove is placed on a combustible floor (eg. wood,
laminate, carpet), a floor plate made of non-combustible
material is required.
This floor plate can be made of different materials such
as safety glass or steel plate. The bottom plate must
overtop the front of the stove by at least 50 cm
(from the combustion chamber opening) and laterally
by at least 30 cm.
The following sketch illustrates the distances in
detail:
13
cook mini
70 cm
40 cm
30 cm
cook mini