Télécharger Imprimer la page

LA NORDICA ROSSELLA PLUS Instructions Pour L'installation, L'utilisation Et L'entretien page 20

Publicité

Les langues disponibles

Les langues disponibles

50 cm
2 m
1
m
CHIMNEY CAPS - DISTANCES AND POSITIONING
Inclination of the roof
α α α α
15°
30°
45°
60°
6.
CONNECTION TO THE CHIMNEY / AIR FOR COMBUSTION
For safety reasons the door of the appliances with constructive system 1, must be opened only for the
loading of the fuel or for removing the ashes, while during the operation and the rest, the door of the hearth
must remain closed.
20
Rossella Plus – Rossella Plus forno / Nicoletta – Nicoletta forno / Gisella
(1) In case of flues side by side, a chimney cap must be higher than the
other one of at least 50 cm in order to avoid pressure transfers between
the flues themselves.
10 m
>A
H min.
(1)ridge axis
α
Distance between the roof
ridge and the stack
A (m)
< 1,85 m
> 1,85 m
< 1,50 m
> 1,50 m
< 1,30 m
> 1,30 m
< 1,20 m
> 1,20 m
(1)
The chimney cap must not show hindrances within 10 m
from walls, pitches and trees. Otherwise raise it of at least 1
m over the hindrance.
The chimney cap must exceed the ridge of the roof of at
least 1 m.
> _ A
0,5 m
(2)roof
Minimum height of the stack (measured
UNI 10683/98
from the outlet)
H (m)
0,50 m above the roof ridge
1,00 m from the roof
0,50 m above the roof ridge
1,30 m from the roof
0,50 m above the roof ridge
2,00 m from the roof
0,50 m above the roof ridge
2,60 m from the roof
Picture 5
Picture 6
Picture 7
7192450 – EN

Publicité

loading

Ce manuel est également adapté pour:

Rossella plus fornoNicolettaNicoletta fornoGisella