COMPLETE TROUBLESHOOTING GUIDE
High Temperature Shut-Off
***IMPORTANT: READ AND FOLLOW THESE INSTRUCTIONS BEFORE
DO NOT CONNECT UNIT BEFORE STEP 1 OF THE TEST.
DO NOT CONNECT A LOAD INTO THE UNIT BEFORE STEP 3 OF THE TEST.
TEMPERATURE: You have to perform this test with the sensor held in
the palm of your hand to simulate a temperature between 30°C and
40°C (86°F and 104°F).
Definitions : CW : Clockwise.
STEP
HANDLING AND TEST DESCRIPTIONS
Plug the unit into the power outlet
while maintaining the temperature
sensor in your hand.
Within 5 seconds:
1
Turn UPPER knob fully CW (High
Temp at 120°F).
Turn LOWER knob fully CCW (Delay
at 0 min.).
8
8
TP3
1 – Before you start
STARTING THE TEST.
CCW : Counter clockwise.
2 – Test
EXPECTED RESULTS
Output On light
indicator turns ON.