LEVEL SWITCH 8110 • With extended status indication
All manuals and user guides at all-guides.com
4 Mounting
4.1 General instructions
Make sure that all parts of the instrument coming in direct contact with
the process, especially the sensor element, process seal and process
fitting, are suitable for the existing process conditions, such as process
pressure, process temperature as well as the chemical properties of
the medium.
You can find the specifications in chapter "Technical data" and on the
nameplate.
In general, LEVEL SWITCH 8110 can be installed in any position. The
instrument only has to be mounted in such a way that the tuning fork is
at the height of the desired switching point.
Keep in mind that the swichting point can vary dependent on the
installation position.
The switching point refers to the medium water (1 g/cm³/0.036 lbs/in³).
Please keep in mind that the switching point of the instrument shifts
when the medium has a density differing from water.
2
1
3
Fig. 2: Mounting vertical
1
Switching point in water
2
Switching point with lower density
3
Switching point with higher density
4 Mounting