9 Supplement
Operation
Plug connections
Signal lamps (LED)
Green
-
Yellow
-
Red
-
Output variable
Output
Load current
Voltage loss
Switching voltage
Blocking current
Mode
Min./Max.
-
Max.
-
Min.
-
Voltage supply
Operating voltage
Power consumption
Electromechanical data
Valve plug ISO 4400
Wire cross-section
-
Outer cable diameter
-
Valve plug ISO 4400 with IDC method of termination
Wire cross-section
-
Single-wire diameter
-
Wire diameter
-
Outer cable diameter
-
Connection frequency
-
Electrical protective measures
Protection rating
Valve plug ISO 4400
-
Valve plug ISO 4400 with IDC method of
-
termination
M12 x 1 plug connection
-
24
All manuals and user guides at all-guides.com
Specification see "Connecting to power supply"
Voltage supply on
Vibrating element covered
Failure
Transistor output PNP
max. 250 mA (output, permanently short-circuit
proof)
< 3 V
< 34 V DC
< 10 µA
Changeover by electronic connection
Overflow protection
Dry run protection
9.6 ... 35 V DC
max. 0.5 W
1.5 mm² (0.06 in²)
4.5 ... 7 mm (0.18 ... 0.28 in)
for wire cross-section of 0.5 ... 1 mm²
(0.02 ... 0.04 in²)
> 0.1 mm (0.004 in)
1.6 ... 2 mm² (0.06 ... 0.08 in²)
5.5 ... 8 mm (0.22 ... 0.31 in)
10 x (on the same cross-section)
IP 65
IP 67
IP 66/IP 67
LEVEL SWITCH 8110 • With extended status indication