Télécharger Imprimer la page

Madas XV-1 Instructions D'installation page 21

Publicité

Les langues disponibles

Les langues disponibles

9.0 - RATING PLATE DATA
The user is obliged to keep the marking of the valve clearly visible: any
coatings or paintwork performed on the product that make the valve
unidentifiable are not to be attributed to the manufacturer.
The rating plate data (see example provided here) includes the following:
• Manufacturer's name/logo and address (possible distributor name/logo)
• Mod.:
• CE-51CR4682
• Cl. A
• Gr. 2
• EN 161
• P.max
• PS
• IP....
• 230V....
• Example of electrical absorption indication: 270/70 VA indicates 270 VA at start, 70 VA at steady state
• TS
(if it is present) = Conformity with PED Dir. followed by Notified Body No.
• year
• Lot
• U1802
• 1065
• 00001
Regulation (EU)
2016/426
PED Directive
2014/68/EU
* Component designed for industrial use in industrial sites.
Madas Technical Manual - 1|1.5cX - REV. 1 of 10
All manuals and user guides at all-guides.com
= device name/model followed
by the connection diameter
= certification pin number
= Seal strength in counterflow at 150 mbar in
accordance with EN 161
= Mechanical resistance group 2 in accordance with EN 161
= Product reference regulation
= Maximum pressure at which product operation is guaranteed
= Allowable maximum pressure
= Protection rating
= Power supply voltage, frequency (if Vac), followed by electrical absorption
= Temperature range within which product operation is guaranteed
= Conformity with Regulation (EU) 2016/426 followed by Notified Body No.
= In compliance with ATEX followed by the protection mode
(complete protection mode indicated on coil and CPI switch)
= Year of manufacture
= Product serial number (see explanation below)
= Lot issued in year 2018 in the 2nd week
= progressive job order number for the indicated year
= progressive number referring to the quantity of the lot
P. max 0.5 bar
-
-
Sep 2020
th
Mod: XV-1 DN 100
CE- 51CR4682 CI.A GR.2 EN 161
IP65 – 230 V/50-60 Hz 270/70 VA
year: 2018
Compliance table
P. max 1 bar
-
21
P. max=PS=1 bar
TS: -20+60 °C
II 3G
0051
II 3D
0497
Lot:U1802
1065/00001
P. max 3 - 6 bar
*
*
*
XV(F)-1-3-6

Publicité

loading

Ce manuel est également adapté pour:

Xv-3Xv-6Xvf-1Xvf-3Xvf-6