All manuals and user guides at all-guides.com
Product specific information for use with floorheating
systems
• Use with T2QuickNet:
The T2QuickNet product line is approved with the
thermostat working in floor sensor mode. Be aware that
the floor sensor must be installed and activated for an
installation with T2QuickNet.
• Use with T2Red (T2Reflecta) self-regulating systems:
Self-regulating heating cables have an inrush current
at start up. In order to guarantee the life time of the
thermostat, the maximum load of the self-regulating
application in nominal conditions is limited to 10A.
A 13A self-regulating load will reduce the life time of the
relay contacts.
Direct, connection – e.g. single heating circuit
Remote set
back signal
NTC
10K
8
Power supply
Floor
230 VAC
sensor
L N PE
FP
L N
N
Heating cable
230 VAC
Max.13A
L
N
PE
L
PE