Simple venting configuration
EN
(only two 90° elbows)
For vent configurations requiring more than two 90° elbows, the following formulas apply:
Formula 1: H
T
Formula 2: H
T
Example:
V
= 4 FT (1.2m)
1
V
= 1.5 FT (0.5m)
2
V
= V
+ V
= 4FT (1.2m) + 1.5FT (0.5m) = 5.5 FT (1.7m)
T
1
2
H
= 2 FT (0.6m)
1
H
= 1 FT (0.3m)
2
H
= 1 FT (0.3m)
3
H
= 1.5 FT (0.5m)
4
H
= H
+ H
+H
R
1
2
H
= .03 (four 90° elbows + one 45° elbow - 90°)
O
= .03 (90 + 90 + 90 + 90 + 45 - 90) = 9.45 FT (2.9m)
H
= H
+ H
= 5.5FT (1.7m) + 9.45FT (2.9m) = 14.95FT (4.6m)
T
R
O
H
+ V
= 14.95FT (4.6m) + 5.5FT (1.7m) = 20.45FT (6.2m)
T
T
Formula 1:
Formula 2:
Since both formulas are met, this vent configuration is acceptable.
W415-0788 / F / 10.21.13
< 3.5V
T
+ V
< 24.75 feet (7.5m)
T
+H
= 2FT(0.6m) + 1FT(0.3m) + 1FT(0.3m) + 1.5FT(0.5m) = 5.5 FT(1.7m)
3
4
H
< 3.5V
T
T
3.5V
= 3.5FT (1.1m) x 5.5FT (1.7m) = 19.25FT (5.9m)
T
14.95 FT (4.6m) < 19.25 FT (5.9m)
H
+ V
< 24.75 FT (7.5m)
T
T
20.45 FT (6.2m) < 24.75 FT (7.5m)
(H
) > (V
)
T
T
See graph to determine the required vertical rise V
150(3810)
147 (3733.8
REQUIRED
VERTICAL RISE IN
100 (2540)
INCHES
(MILLIMETERS)V
T
66
(1676.4)
50 (1270)
12
(304.8)
0
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
required horizontal run H
.
T
2.5
5
7.5
10
12.5
(0.8)
(1.5)
(2.3)
(3.1)
(3.8)
1
3.5
(0.3)
(1.1)
values for H
and H
T
T
90°
V
2
90°
H
2
V
1
H
1
90°
16.3_2B
for the
T
15
17.5
20
(4.6)
(5.3)
(6.1)
19.25
(5.9)
T
H
3
90°