Télécharger Imprimer la page
Bryant OBM098 Instructions D'installation
Bryant OBM098 Instructions D'installation

Bryant OBM098 Instructions D'installation

Fournaise au mazout multi-position, puissance de l'entrée 70,000-98000
Masquer les pouces Voir aussi pour OBM098:

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

OBM098
OVM098
Copyright 2011 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
All manuals and user guides at all-guides.com
Installation Instructions
THIS BOOKLET CONTAINS
IMPORTANT INFORMATION
C
INPUT CAPACITIES 70,000---98,000
INSTALLER:
booklet to install the appliance and affix this
booklet
adjacent
installation.
USER:
Keep this booklet of information for
future reference.
SERVICER: Use the information in this booklet
to service the appliance and affix the booklet
adjacent to the appliance after servicing.
A09492
Use of the AHRI Certified TM Mark indicates a
US
manufacturer's participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
Printed in U.S.A.
Edition Date: 07/11
MULTIPOISE OIL FURNACE
Use the information in this
to
the
appliance
Catalog No: IM---OBM098---03 / X40166 Rev. E
Replaces: IM--- OBM098--- 02
after

Publicité

loading

Sommaire des Matières pour Bryant OBM098

  • Page 1 For verification of certification for individual products, go to www.ahridirectory.org. Catalog No: IM---OBM098---03 / X40166 Rev. E Copyright 2011 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 07/11 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 2 All manuals and user guides at all-guides.com TABLE OF CONTENTS SAFETY REGULATIONS ..........................4 SAFETY LABELING AND WARNING SIGNS ..................4 IMPORTANT INFORMATION ........................ 4 DETECTION SYSTEMS ......................... 4 DANGER OF FREEZING........................4 2. INSTALLATION..............................5 POSITIONING THE FURNACE ......................5 CONFIGURATIONS ..........................
  • Page 3 All manuals and user guides at all-guides.com TABLES Table 1: Blower speed adjustments (4-speed motors) ..............9 Table 2: Supply air adjustments, ECM variable speed motors, heating mode ......10 Table 3: Supply air adjustments, ECM variable speed motors, air conditioning mode..10 Table 4: CFM adjustments, all modes ..................10 Table 5: Delay adjustments - heating mode ................10 Table 6: Technical specifications ....................15...
  • Page 4 All manuals and user guides at all-guides.com Before calling for service, be sure to have the 1. SAFETY REGULATIONS information page in section 5 of your manual close by in order to be able to provide the contractor with the required information, such as the model 1.1 SAFETY LABELING AND and serial numbers of the furnace.
  • Page 5 All manuals and user guides at all-guides.com The unit must be installed in an area where the ambient 2. INSTALLATION and return air temperatures are above 15°C (60°F). In addition, the furnace should be installed as closely as This furnace is a true multi-position unit, in that it will function possible to the vent, so that the connections are direct and in an upflow, downflow or horizontal configuration to the left or kept to a minimum.
  • Page 6 All manuals and user guides at all-guides.com Figure 4: Horizontal installation 2.2.2 Downflow Installation When the furnace is installed in the downflow position on a Floor Return Burner combustible floor, the clearances from combustibles must be adhered to. The downflow base DFB-102 or KLASB0801DET can be used to ensure these clearances.
  • Page 7 All manuals and user guides at all-guides.com Complete oil line connections. 2.5.1 Nozzles The burner comes equipped with an appropriate nozzle. However, if another size or a replacement nozzle is required, use the manufacturer’s recommended spray angle and type a shown in Table 6 and based on a pump pressure of 100 psi.
  • Page 8 All manuals and user guides at all-guides.com 2.6.1 Masonry chimney Start up the burner; This furnace can be vented into an existing masonry chimney. Remove the three-pole plug from the BVSO outlet on However, the unit must not be vented into a chimney into the furnace;...
  • Page 9 All manuals and user guides at all-guides.com Halogen type refrigerants; 2.10 DUCTING Cleaning solvents (such as perchloroethylene); Printing inks, paint removers, varnishes, etc. ; WARNING Hydrochloric acid; Solvent based glue; Poisonous carbon monoxide gas hazard. Antistatic fabric softeners for clothes dryers; DO NOT draw return air from inside a closet or utility m.
  • Page 10 All manuals and user guides at all-guides.com Table 5: Delay adjustments - heating mode Figure 8: Blower start/stop delays SW4 – Delay Input DIP Switch Positions Board # 1158 USGPH POSITION 0.70 0.60 0.50 2.13 INSTALLATION OF ACCESSORIES WARNING Electrical shock hazard. Turn OFF electrical power at the fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before...
  • Page 11 All manuals and user guides at all-guides.com 2.13.3 Air Conditioner (or Heat Pump) OPERATING SEQUENCE An air conditioning coil may be installed on the supply air side OIL HEATING MODE ONLY. The W-R contact closes; The burner motor starts up to pre-purge the WARNING combustion chamber for a period of 10 to 15 seconds.
  • Page 12 All manuals and user guides at all-guides.com The total vent temperature should be between 204 3.3.3 Combustion Check and 302°C (400 and 575°F). If not, check for improper air temperature rise, pump pressure, nozzle size or a IMPORTANT badly sooted heat exchanger. The heat exchanger metal surfaces may have oil and the baffle insulation also contains binders.
  • Page 13 All manuals and user guides at all-guides.com CLEANING THE BLOCKED VENT MAINTENANCE SHUT-OFF DEVICE (BVSO) WARNING For continuous safe operation, the Blocked Vent Shut-off device (BVSO) must be inspected and maintained annually by a qualified service technician. Electrical shock hazard. Disconnect power to the appliance;...
  • Page 14 All manuals and user guides at all-guides.com 5 FURNACE INFORMATION Model: Serial number: Furnace installation date: Service telephone #-Day: Night: Dealer name and address: START-UP RESULTS Nozzle: Pressure: Lb/in Burner adjustments: Primary air Fine air Drawer Assembly Smoke scale: (Bacharach) Gross stack temperature: °F Ambient temperature:...
  • Page 15 All manuals and user guides at all-guides.com Table 6: Technical specifications MULTI POSITIONS MODELS - SERIES 098 UNITS WITH 1/3 HP PSC MOTOR UNITS WITH 1/2 HP ECM MOTOR RATING AND PERFORMANCE Firing rate (USGPH)* 0,50 0,60 0,70 0,50 0,60 0.70 Input (BTU/h)* 70 000...
  • Page 16 All manuals and user guides at all-guides.com Table 7: Airflow data, models with 1/2 HP ECM motors OIL HEATING MODE 24 VAC input (R) on W only SW1- HEAT HEAT INPUT CFM with SW3-ADJ CFM with SW3-ADJ CFM with SW3-ADJ DIP switch position (USGPH) DIP switch position A...
  • Page 17 All manuals and user guides at all-guides.com Table 8: Airflow data, models with 1/3 HP PSC motors External Static Pressure ("W .C.) Speed HIGH 1230 1185 1150 1095 1050 MED-HIGH 1090 1055 1005 MED-LOW Table 9: Minimum clearances from combustible materials LOCATION UPFLOW HORIZONTAL...
  • Page 18 All manuals and user guides at all-guides.com Figure 9: Furnace dimensions...
  • Page 19 All manuals and user guides at all-guides.com Figure 10: Wiring diagram, 4-speed motor (PSC)
  • Page 20 All manuals and user guides at all-guides.com Figure 11: Wiring diagram, variable speed motor (ECM)
  • Page 21 All manuals and user guides at all-guides.com COMPONENTS REPLACEMENT PARTS...
  • Page 22 All manuals and user guides at all-guides.com Figure 12: Parts list with 4-speed motor (PSC) B50064G...
  • Page 23 All manuals and user guides at all-guides.com Table 10: Parts list with 4-speed motor (PSC) ITEM PART # DESCRIPTION COMMENTS B03409 HEAT EXCHANGER Heat exchanger only J06L002 SEAL STRIP, 1/4 x 1/8 x 25' B03429 WIRE CHANNEL, INT. B03420-01 FRONT PANEL ASSEMBLY Panel, insulation and labels included B03444 FRONT PANEL INSULATION...
  • Page 24 All manuals and user guides at all-guides.com Figure 13: Parts list with variable speed motor (ECM) B50074H...
  • Page 25 All manuals and user guides at all-guides.com Table 11: Parts list with variable speed motor (ECM) ITEM PART # DESCRIPTION COMMENTS B03409 HEAT EXCHANGER Heat exchangeur only J06L002 SEAL STRIP, 1/4 x 1/8 x 25' B03429 WIRE CHANNEL, INT. B03420-01 FRONT PANEL ASSEMBLY Panel, insulation and labels included B03444...
  • Page 26 For verification of certification for individual products, go to www.ahridirectory.org. Catalog No: IM---OBM098---03FR / X40166 Rev. E Copyright 2011 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in Canada. Edition Date: 07/11 Le manufacturier se réserve le droit de modifier, à...
  • Page 27 All manuals and user guides at all-guides.com TABLE DES MATIÈRES 1 RÈGLES DE SÉCURITÉ ..................4 SIGNALISATION DANGER, MISE EN GARDE ET AVERTISSEMENT ....4 REMARQUES IMPORTANTES ................4 SYSTÈMES DE PROTECTION ................4 RISQUE DE GEL ....................5 2 INSTALLATION....................5 EMPLACEMENT....................
  • Page 28 All manuals and user guides at all-guides.com FIGURES Figure 1: Dimensions et localisation, ouvertures de ventilation dans la porte du placard ........................ 6 Figure 2: Débit ascendant ......................6 Figure 3: Débit descendant......................6 Figure 4: Débit horizontal......................6 Figure 5: Branchement du thermostat, chauffage et climatisation , unité avec moteur 4 vitesses......................
  • Page 29 All manuals and user guides at all-guides.com 1 RÈGLES DE SÉCURITÉ e) Ne jamais obstruer les grilles de retour d’air ou le filtre. f) Demander à l’installateur d'identifier et de SIGNALISATION DANGER, MISE EN vous informer sur les items suivants : GARDE ET AVERTISSEMENT L’interrupteur d’alimentation électrique ;...
  • Page 30 All manuals and user guides at all-guides.com 2.1 EMPLACEMENT RISQUE DE GEL MISE EN GARDE AVERTISSEMENT Si votre appareil demeure fermé durant la saison Risque d’incendie ou d'explosion. froide, les conduites d’eau peuvent geler, éclater et L’appareil doit être installé au niveau. Ne jamais provoquer des dégâts d’eau importants.
  • Page 31 All manuals and user guides at all-guides.com de protection. Dans le cas où l’entrée d’air se fait par Figure 1: Dimensions et localisation, ouvertures le plancher, utiliser la "Base pour un retour par le ventilation dans la porte du placard plancher"...
  • Page 32 All manuals and user guides at all-guides.com Figure 6: Branchement du thermostat, chauffage 2.3 RACCORDEMENT ÉLECTRIQUE et climatisation unité avec moteur ECM AVERTISSEMENT L’extérieur de l’unité doit posséder une mise à la terre ininterrompue pour minimiser les risques de blessures corporelles si jamais un problème électrique se produisait.
  • Page 33 All manuals and user guides at all-guides.com 2.5 INSTALLATION DU BRÛLEUR 2.6 ÉVACUATION Veuillez vous référer aux instructions fournies par le MISE EN GARDE fabriquant du brûleur pour plus de détails. De plus, le brûleur doit toujours être installé du même sens peu importe Risque d’empoisonnement par monoxyde de l’orientation de la fournaise.
  • Page 34 All manuals and user guides at all-guides.com 2.6.4 Évacuation directe murale APPROVISIONNEMENT EN AIR DE L’unité de chauffage est approuvée avec un système COMBUSTION ET VENTILATION d’évacuation directe murale. Ce système comprend un MISE EN GARDE évacuateur mural modèle VTK-098/KLAVT0101DET et un tuyau d’évacuation isolé...
  • Page 35 All manuals and user guides at all-guides.com Agents chimiques pour piscine à base de chlore ; 2.10 SYSTÈME DE DISTRIBUTION Agents chimiques adoucisseur d’eau ; D’AIR Sels ou agents chimiques pour le déglaçage ; MISE EN GARDE Tetrachlorine de carbone ; Fluides frigorigènes halogénés ;...
  • Page 36 All manuals and user guides at all-guides.com Tableau 3: Ajustements des débits d'air, mode Pour faire l’ajustement, les fils ROUGE (chauffage) et BLEU climatisation (climatisation ou thermopompe) peuvent être déplacés sur le moteur. Vérifier aussi que la position des fils sur le contrôle électronique de l’unité...
  • Page 37 All manuals and user guides at all-guides.com L’ajustement des vitesses de ventilation en 2.13.2 Filtre électronique (EAC) chauffage et climatisation sont adéquats et selon les spécifications de ce manuel. Le terminal EAC sur le contrôle électronique de l'appareil Les délais de départ et d’arrêt du ventilateur fourni un signal 120 VAC lorsque le ventilateur fonctionne sont réglés de façon satisfaisante.
  • Page 38 All manuals and user guides at all-guides.com prévus à cet effet. Référer au manuel d’instruction du 3.3.5 Test de pression dessus feu brûleur. La pression au-dessus de la flamme, mesurée à travers la fenêtre d'observation (située au centre, au dessus du brûleur, dans le panneau avant de 3.3.3 Vérification de la combustion l'appareil de chauffage central), est requise pour...
  • Page 39 All manuals and user guides at all-guides.com Ajuster thermostat dessus 3.3.8 Vérification des limiteurs de température température ambiante ; Après que l’appareil de chauffage central ait fonctionné Si l’allumage du brûleur de s’effectue pas, durant au moins 15 minutes, restreindre l’entrée d’air en couper l’alimentation électrique et appeler un bloquant les filtres ou en fermant les registres de retour d’air technicien qualifié.
  • Page 40 All manuals and user guides at all-guides.com 4.5 REMPLACEMENT DU FILTRE AVERTISSEMENT À L’HUILE Ne pas érafler ou égratigner la surface de l’interrupteur Filtre du réservoir thermique. Un interrupteur thermique endommagé doit être remplacé. Remplacer le filtre du réservoir au besoin. Suivre les instructions du fabriquant.
  • Page 41 All manuals and user guides at all-guides.com Tableau 6: Spécifications techniques MODÈLES MULTIPOSITION, SÉRIE 098 UNITÉ AVEC MOTEUR 1/3 HP PSC UNITÉ AVEC MOTEUR 1/2 HP ECM TAUX ET PERFORMANCE Allure de chauffe (USGPH)* 0,50 0,60 0,70 0,50 0,60 0,70 Consommation (BTU/h)* 70 000 84 000...
  • Page 42 All manuals and user guides at all-guides.com Tableau 7: Débits d'air, unités avec moteur 1/2 HP ECM MODE DE CHAUFFAGE AU MAZOUT Signal 24 VAC (R) sur W seulement SW1- Chauffage Consommation PCM avec interrupteur PCM avec interrupteur PCM avec interrupteur Position Chauffage DIP "SW3-ADJ",...
  • Page 43 All manuals and user guides at all-guides.com Tableau 8: Débits d'air, unités avec moteur 1/3 HP PCM PRESSION ST ATIQUE EXT ERNE ("C.E.) VITESSE HIGH 1230 1185 1150 1095 1050 MED-HIGH 1090 1055 1005 MED-LOW Tableau 9: Dégagements minimums aux matériaux combustibles APPLICATION ASCENDANT HORIZONTAL DESCENDANT FOURNAISE...
  • Page 44 All manuals and user guides at all-guides.com Figure 9: Dimensions de la fournaise...
  • Page 45 All manuals and user guides at all-guides.com Figure 10: Diagramme électrique, moteur 4 vitesses (PSC)
  • Page 46 All manuals and user guides at all-guides.com Figure 11: Diagramme électrique, moteur vitesse variable (ECM)
  • Page 47 All manuals and user guides at all-guides.com COMPOSANTES PIÈCES DE REMPLACEMENT...
  • Page 48 All manuals and user guides at all-guides.com Figure 12: Liste de pièces avec moteur 4 vitesses (PSC) B50064G...
  • Page 49 All manuals and user guides at all-guides.com Tableau 10: Liste de pièces avec moteur 4 vitesses (PSC) COMMENTAIRES ITEM DESCRIPTION No DESSIN B03409 ASS ECHANGEUR CHALEUR Échangeur seulement J06L002 JOINT EXTRUDE 1/4 x 1/8 x 25' B03429 CACHE FIL INT. B03420-01 ASS PANNEAU AVANT Comprend panneau, isolation et libelles...
  • Page 50 All manuals and user guides at all-guides.com Figure 13: Liste de pièces avec moteur vitesse variable (ECM) B50074G...
  • Page 51 All manuals and user guides at all-guides.com Tableau 11: Liste de pièces avec moteur vitesse variable (ECM) ITEM No DESS DESCRIPTION COMMENTAIRES B03409 ASS ECHANGEUR CHALEUR Échangeur seulement J06L002 JOINT EXTRUDE 1/4 x 1/8 x 25' B03429 CACHE FIL INT. B03420-01 ASS PANNEAU AVANT Comprend panneau, isolation et libelles...

Ce manuel est également adapté pour:

Ovm098