Wiring Diagram / Schéma Unifiliare
6-2/0
AL/CU
GRD
WHEN
REQ'D
3 Phase - 225A MAX
USE COPPER OR ALUMINUM WIRE
Use 60ºC or 75ºC ampacity sized wire on
line and neutral and equipment ground
terminals, except as noted below
• Refer to circuit breakers for allowable
wire temperature rating, wire size and
tightening torque, except as noted
below.
• Use #1 awg. Maximum, 75ºC wire for
90a and 100A horizontal mounted
q-line breakers only.
• Use #3 awg. Maximum 75ºC, copper
only wire for 90-100A q-line breaker
& tey main breakers horizontally
mounted in a 7 5/8" wide box
• Use #3 awg, maximum 60ºC, copper
only wire for tey 80A, max. Horizontally
mounted branch breakers.
A-Series Lighting Panels Rating Labels
LINE
6-2/0
AL/CU
GRD
WHEN
REQ'D
LINE
1 Phase - 225A MAX
LE CUIVRE D'USAGE OU LE FIL
D'ALUMINIUM
L'usage 60ºC ou 75º ampacity de c a
calibre le fil connectee et neutre et
terminaux de sol d'equipement, sauf
comme repute au dessous
• Se referer aux disjoncteurs pour
le classement de temperature de
fil admissible, a la taille de fil et a
resserrer le moment de torsion, sauf
comme repute au dessous
• l'usage #1 awg. Le maximum, 75ºle fil
de c pour l'horizontale de 90a et 100A
a monte les concasseurs de q-ligne
seulement.
• l'usage #3 awg. Le maximum 75ºle c,
le cuivre seulement fil pour 90-100A
concasseur de q-ligne & tey les
concasseurs principaux ont monte
horizontalement dans un 7 5/8" la
boite large
• l'usage #3 awg, le maximum 60ºle
c, le cuivre seulement fil pour tey
80A, le maximum. Les concasseurs
horizontalement de branche montes.
28