7. Remove the pilot hood from the pilot assembly
by pulling vertically. Use a
/
5
32
the pilot injector. Replace the pilot injector with the
one supplied. Re-assemble the pilot hood onto the
assembly ensuring key position for proper alignment.
8. The conversion data label must be filled out and
attached adjacent to the valve.
9. Turn on the gas supply and check for gas leaks by
brushing on a soap and water solution. Do not use
open flame.
VENTURI ADJUSTMENT
Air shutters have been factory set open according to the chart below.
These setting are for (maximum) horizontal termination.
NG
1/16" (1.6mm) FRONT
P
7/16" (11.1mm) FRONT
NG
1/16" (1.6mm) FRONT
P
7/16" (11.1mm) FRONT
Adjustment may be required depending on fuel type, vent configuration and
altitude.
Air shutter adjustment must be done by a qualified
Closing the air shutter will cause a
more yellow flame, but can lead to
carboning. Opening the air shutter will
cause a more blue flame, but can cause
flame lifting from the burner ports. The flame
may not appear yellow immediately; allow
15 to 30 minutes for the final flame colour to be
established.
It is important to periodically perform a visual check of the pilot and burner flames.
Compare them to the illustrations provided.
LOG VERSION
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 0G8 Canada
All manuals and user guides at all-guides.com
" Allen key to unscrew
ADJUSTMENTS
B35TL
1/16" (1.6mm) REAR
1/4" (6.4mm) REAR
B52TL
1/16" (1.6mm) REAR
1/4" (6.4mm) REAR
installer!
AIR SHUTTER
ADJUSTMENT
CLOSED
OPEN
FLAME CHARACTERISTICS
10. Re-install the valve train, burner and media try. Then light the pilot and
PILOT
HOOD
main burner to ensure that the gas lines have been purged.
lines with the glass door off.
appliance installation manual. Once all systems have been checked, replace
PILOT
the glass media.
INJECTOR
Assure that a continuous flow is at the burner before re-
11.
securing the door
SPRING
CLIP
Adjust the pilot screw to provide properly sized flame. Turn in a clockwise
direction to reduce the gas flow.
Inlet pressure can be checked by turning screw (A) counter-clockwise until
loosened and then placing pressure gauge tubing over the test point. Gauge
should read 7" (minimum 4.5") water column for natural gas or 13" (11" minimum)
water column for propane. Check that main burner is operating on "HI".
Outlet pressure can be checked the same as above using screw (B). Gauge
should read 3.5" water column for natural gas or 10" water column for propane.
Check that main burner is operating on "HI".
AFTER TAKING PRESSURE READINGS, TIGHTEN SCREWS FIRMLY TO
SEAL. DO NOT OVER TORQUE.
LEAK TEST.
B35TL
B52TL
GLASS VERSION
• 1(866)820-8686
Refer to the lighting instructions in your
. Then, turn on the electrical supply to the appliance.
PRESSURE ADJUSTMENT
B
A
PILOT SCREW
Maximum Input Ratings:
NG
P
35,000 btu/hr
35,000 btu/hr
55,000 btu/hr
55,000 btu/hr
PILOT
ELECTRODE
BURNER
3/8" - 1/2"
(9.5mm - 12.7mm)
FLAME
SENSOR
FLAME MUST ENVELOP
UPPER 3/8" (9.5mm) TO 1/2"
(12.7mm) OF FLAME SENSOR