3.3.5 Connection between the single cabinet
KEOR HP 400kVA
Power connections
between CABINET 1 (Static switch) and CABINET 2 (Rectifier/Inverter)
Cables or bars to connect
Flex bar
Cable
Mobile connector 21N
Flex bar
Ground cable yellow/green
Signal connections
between CABINET 1 (Static switch) and CABINET 2 (Rectifier/Inverter)
Cables to connect
Mobile connector CN1/CN2/CN3
Mobile connector W22/N
Flat
KEOR HP 500-600kVA
Power connections
between CABINET 1 (Static switch) and CABINET 2 (Rectifier/Inverter)
Cables or bars to connect
Flex bar
Cable
Mobile connector 21N
Flex bar
Earth cable yellow/green
Signal connections
between CABINET 1 (Static switch) and CABINET 2 (Rectifier/Inverter)
Cables to connect
Mobile connector CN1/CN2/CN3
Mobile connector W22/N
Flat
30
OMD39075 REV. F
Installation and start-up of UPS Keor Hp 400-800kVA
Installation et démarrage de l'UPS Keor Hp 400-800 kVA
Installazione e avviamento UPS Keor Hp 400-800kVA
4/5/6
21
22/23/24
W10/W11/W12
W10A/W11A/W12A
W53/W54/W55/W61
+R/46/-R
21
22/23/24
W10/W11/W12
W10A/W11A/W12A
Notes
Connect to EMI FILTER
Connect to neutral copper bar (2N-3N)
Connect to respective permanent connector
Connect to terminals 22/23/24
Connect to screw M10
Notes
Connect to respective permanent connector
Connect to respective identified connector
Connect to J2 connector in their Flat-Flat board
Notes
Connect on the +R/46/-R copper bar in the
respective points identified
Connect to neutral copper bar (2N-3N)
Connect to respective permanent connector
Connect to terminals 22/23/24
Connect to screw M10
Notes
Connect to respective permanent connector
There is CN3 connector only with some option
Connect to respective identified connector
Connect to J2 connector in their flat-flat board