Classification of chemically active substances (EN 60721-3-3)
Environmental parameter
a)
Sea salt
b)
Sulphur dioxide
c)
Hydrogen sulphide
3
d)
Chlorine [mg/m
]
e)
ydrochloric acid
H
f)
ydrofluoric acid
H
3
g)
Ammonia [mg/m
]
3
h)
Ozone [mg/m
]
i)
Nitric oxide (expressed in equivalent values of
nitrogen dioxide) [mg/m
Places where atmosphere is strictly monitored and
regulated ("clean spaces" category)
Places where atmosphere is permanently
monitored
Places located in rural and urban
industrial activities are few and where traffic
is moderate
Places located in urban regions with industrial
activities and/or considerable traffic
Places in proximity to industrial sources with
chemical emissions
Places located in industrial installations.
Emissions of highly concentrated chemical
pollutants
UPS KEOR HP is designed to be installed in an environment that meets the following
classifications.
K
Climatic conditions
B
Biological conditions
C
Chemically active substances
S
Mechanically active substances
In the event that the environmental conditions of the installation room do not comply with the
specified requirements, additional precautions must be taken to reduce excessive values to the
specified limits.
3
[mg/m
]
3
[mg/m
]
3
[mg/m
]
3
[mg/m
]
3
]
regions where
Class
3C1R
3C1L
3C1
No
No
No
0,01
0,1
0,1
0,0015
0,01
0,01
0,001
0,01
0,1
0,001
0,01
0,1
0,001
0,003
0,003
0,03
0,3
0,3
0,004
0,01
0,01
0,01
0,1
0,1
X
X
X
In accordance with the technical
specification
3B1 (EN 60721-3-3)
3C2 (EN 60721-3-3)
3S2 (EN 60721-3-3)
3C2
3C3
3C4
Salt
Salt
Salt
fog
fog
fog
1,0
10
0,5
10
0,3
1,0
3,0
0,5
5,0
5,0
0,03
2,0
2,0
3,0
35
175
0,1
0,3
2,0
1,0
9,0
X
X
OMD39075 REV. F
40
70
20
X
29