Installation and start-up of UPS Keor Hp 400-800kVA
Installation et démarrage de l'UPS Keor Hp 400-800 kVA
Installazione e avviamento UPS Keor Hp 400-800kVA
3.3.3 Minimum distances from the walls and ventilation
The UPS must be so installed as to ensure its serviceability and to allow a correct air flow as
much as possible.
With regard to the minimum distances from the walls, for all of the UPS sizes the same
installation conditions apply as indicated in the table below.
Picture 11 – Minimum distances from the walls
The table below shows the air volume required for an optimal ventilation and cooling of the
UPS.
Power (kVA)
Air volume (m
A (mm)
B (mm)
1000
400
3
/h)
3500
D (mm)
700
50
500
600
4000
4500
800
7000
OMD39075 REV. F