Initial operation
See 5.6 for a description of the cont5.5 panel
During commissioning, the following input is expected:
1. Language for the display
2. Date / Time
3. Product type
4. Maintenance interval
* When using the product as a redundancy control unit (with the hybrid lifting station Ecolift XL), when configuring
the control unit you must select the entry „Redundancy Control Unit" in the menu „product type". Otherwise the
connection between the two control units cannot be established. Comply with instructions that accompany the hybrid
lifting station.
4.1
Carrying out initialisation
Supply the control unit with mains voltage, a self-test is performed
with the following steps
– Activation of alarm-power outage battery
– Green LED Ready for operation  <19> comes on
– The backwater flap is closed electrically and then opened again
(yellow LED <22> backwater flap flashes during the flap movement
and goes out when the backwater flap is open)
– Menu 3.10
If initial operation (menu 0.1. Language) is not included on the display, the control unit has already been
parameterised. In this case, the parameters set must be checked or the unit must be reset to the factory setting (see
chapter 5.6, item 3.11).
When the factory settings have been reset, initial operation of the control unit is automatically offered.
The counters for the maintenance interval and switching cycles are ignored during the reset.
Press the OK <69> button, the display lighting is switched on
Select and save the national language, the menu
Set and save the date and time (24-hour format), the menu
Select the product type, save and follow the further instructions in the display until the menu
appears
Select the maintenance interval or set this individually and save, a self-test is carried out. The LEDs come on
alternately while the electrical components (backwater flap) are checked. The System info menu then appears for a
few seconds*, initial operation has now been completed
* The control unit then switches to the automatic mode
2019/04
All manuals and user guides at all-guides.com
Initial operation
Language
appears
Date/Time
appears
Product type
appears
39 / 148
19
FLAP
Ill. [13]
Maintenance interval