Installation Instruction
While still hot, compress the end of the tube using pliers and hold for 5 seconds.
Now, put the outer heat shrink tube (length: 2 ¾" (70 mm); diameter: ¾" (19 mm)) over the end of
the trace heater.
Make sure that it overlaps the bared part of the trace heater for ¾" (20 mm).
Beginning at the end of the cable, shrink the tube at a temperature of 275 °F / 135 °C.
088L1457 & AN296061216351en-US0102
End-termination - Heat shrink technology connection system
4
5
© Danfoss | 2021.11 | 8