Installation Instruction
Installation of the end seal
Cut the trace heater off straight.
Remove 1 ¼" (30 mm) of the outer jacket on the trace heater.
Remove the exposed grounding braid. Make sure that the insulation jacket is not damaged.
Cut in a triangle (⅜" (5 mm)) between the bus wires.
Put the inner heat shrink tube for the end-termination (length: ¾" (20 mm);
diameter: ½" (12 mm) over the end of the trace heater.
Leave an overlap of ⅝"(15 mm).
Beginning at the end of the cable, shrink the tube at a temperature of 275 °F / 135 °C.