Fig. 4
Break out thin section of cover when wiring both switches from one
conduit entrance.
Fig. 6
Typical Electrical Connections
Notes:
1. The Model VSR-SG has two switches, one can be used to operate a
central station, proprietary or remote signaling unit, while the other
contact is used to operate a local audible or visual annunciator.
2. For supervised circuits, see "Switch Terminal Connections"
drawing and warning note (Fig. 5).
Testing
The frequency of inspection and testing for the Model VSR-SG and its associated protective monitoring system shall be in accordance with applicable
NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
If provided, the inspector's test valve shall always be used for test purposes. If there are no provisions for testing the operation of the fl ow detection
device on the system, application of the VSR-SG is not recommended or advisable.
A minimum fl ow of 10 GPM (38 LPM) is required to activate this device.
Advise the person responsible for testing of the fire protection system that this system must be tested in accordance
with the testing instructions.
Fig. 7 Mounting Dimensions
3.50 in
(89.0 mm)
PIPE
PLASTIC PADDLE
PRINTED IN USA
FOR CPVC PIPE
DWG# 1205-4
5.56 in
(141.2 mm)
2.00 in
(50.8 mm)
3.91 in
(99.33 mm)
MFG. #5401190 - REV D
firealarmresources.com
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
AND GLUE-IN UNION
Fig. 5
Switch Terminal Connections Clamping Plate Terminal
An uninsulated section of a single conductor should not be looped
around the terminal and serve as two separate connections. The
wire must be severed, thereby providing supervision of the
connection in the event that the wire become dislodged from under
the terminal. Failure to sever the wire may render the device
inoperable risking severe property damage and loss of life.
Do not strip wire beyond 3/8" of length or expose an uninsulated
conductor beyond the edge of the terminal block. When using
stranded wire, capture all strands under the clamping plate.
DWG. 1146-12
Fig. 8
DWG# 1190-1
9/09
VSR-SG
BELL
POWER SOURCE
SUITABLE FOR BELL
WATERFLOW ZONE
EOLR
ON FIRE PANEL
GREEN GROUND
SCREWS
DWG# 1205-15
DWG# 1205-15
PAGE 3 OF 8