R
Specifi cations subject to change without notice.
Stock Number: 1144461
Optional: Cover Tamper Switch Kit, stock no. 0090148
Replaceable Components: Retard/Switch Assembly, stock no. 1029030
General Information
The Model VSR-SG is a vane type waterfl ow switch for use on wet
sprinkler systems using CPVC plastic fi ttings (manufactured by Tyco,
Nibco, Victaulic, Ipex, and Spears Manufacturing Company) that use 1",
1 ¼", 1 ½", or 2" pipe sizes. It is equipped with a union to accommodate
installation in confi ned spaces.
The VSR-SG contains two single pole, double throw, snap action
switches and an adjustable, instantly recycling pneumatic retard. The
switches are actuated when a fl ow of 10 GPM (38 LPM) or more
occurs downstream of the device. The fl ow condition must exist for a
period of time necessary to overcome the selected retard period.
Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-572-3005 • Tech Support: 866-956-0988 /Canada 888-882-1833 • www.pottersignal.com
PRINTED IN USA
FOR CPVC PIPE
UL, CUL and CSFM Listed
Service Pressure: Up to 175 PSI (12,07 BAR)
Flow Sensitivity Range for Signal:
Maximum Surge:
Contact Ratings:
Conduit Entrances: Two openings provided for 1/2" conduit.
Environmental Specifi cations:
Service Use:
Automatic Sprinkler
One or two family dwelling
Residential occupancy up to four stories
National Fire Alarm Code
• Installation must be performed by qualifi ed personnel and in
accordance with all national and local codes and ordinances.
• Shock hazard. Disconnect power source before servicing. Serious
injury or death could result.
• Risk of explosion. Not for use in hazardous locations. Serious
injury or death could result.
Waterfl ow switches that are monitoring wet pipe sprinkler systems shall
not be used as the sole initiating device to discharge AFFF, deluge,
or chemical suppression systems. Waterfl ow switches used for this
application may result in unintended discharges caused by surges,
trapped air, or short retard times.
Enclosure
The VSR-SG switches and retard device are enclosed in a general
purpose, die-cast housing. The cover is held in place with two tamper
resistant screws which require a special key for removal. A fi eld
installable cover tamper switch is available as an option which may
be used to indicate unauthorized removal of the cover. See bulletin
number 5401103 for installation instructions of this switch.
MFG. #5401190 - REV D
9/09
firealarmresources.com
VSR-SG
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
AND GLUE-IN UNION
18 FPS (5.5 m/s)
Two sets of SPDT (Form C)
10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
10 mAmps min. at 24VDC
Individual switch compartments suitable
for dissimilar voltages.
• NEMA 4/IP54 Rated Enclosure suitable for indoor or
outdoor use with factory installed gasket and die-cast housing
when used with appropriate conduit fi tting.
• Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL
4-10 GPM (15-38 LPM) - UL
NFPA-13
NFPA-13D
NFPA-13R
NFPA-72
PAGE 1 OF 8

Publicité

loading

Sommaire des Matières pour Potter VSR-SG

  • Page 1 The fl ow condition must exist for a period of time necessary to overcome the selected retard period. Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-572-3005 • Tech Support: 866-956-0988 /Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.
  • Page 2 CPVC piping systems. (Note: The 1" male fi tting must bottom out on the stop of the TEE for proper operation of the VSR-SG. See Fig. 1.) Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SG to the 1" male fi tting. Select the proper paddle for the pipe size and type of TEE used.
  • Page 3 DWG. 1146-12 Testing The frequency of inspection and testing for the Model VSR-SG and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
  • Page 4 Maintenance Inspect detectors monthly. If leaks are found, replace the detector. The VSR-SG waterfl ow switch should provide years of trouble-free service. The retard and switch assembly are easily fi eld replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock #1029030 (see Fig.
  • Page 5 Le modèle VSR-SG est un commutateur de débit d’eau à ailettes utilisé avec Boîtier les systèmes d’extincteurs sous eau utilisant des raccords de plastique PVC-C Les commutateurs VSR-SG et le dispositif retardateur sont enfermés...
  • Page 6 à la butée du « T » pour un bon fonctionnement du VSR-SG. Voir la fi g. 1) Attendre 2 à 4 heures pour laisser sécher la colle avant d’installer le VSR-SG au raccord mâle de 1 po (25 mm). Choisir la bonne palette pour la taille de tuyau et le type de « T » utilisé. Voir les fi gures 3 et 5 pour les instruments pour changer la palette.
  • Page 7 Test La fréquence d’inspection et de test du modèle VSR-SG et son système de suivi protecteur associé doit se faire conformément aux normes et codes NFPA applicables et/ou de l’autorité responsable (le fabricant recommande de le faire tous les trimestres ou plus). S’il y a une soupape de test d’inspection qui se trouve normalement à...
  • Page 8 Entretien Vérifi er les détecteurs tous les mois pour y déceler les fuites. En cas de fuite, remplacer le détecteur. Le commutateur de débit d’eau VSR-SG est conçu pour fonctionner pendant des années sans aucun entretien. L’assemblage de commutateur et retardateur se remplace facilement sur le terrain. Dans le cas fort peu probablement de mauvaise performance d’un ou l’autre composant, veuillez commander un assemblage de commutateur retardateur,...

Ce manuel est également adapté pour:

1144461