Installation sequence
-
Push the inlet connector onto the valve block (figure 1)
-
Screw the valve block into the water inlet (figure 2)
-
Insert siphon trap into the outlet (figure 3)
-
Put a battery into the control unit (figure 4a), or plug in the main connections (4b). The LED
flashes.
-
Secure the control unit onto the valve block (figure 5A)
-
Connect the control unit to the siphon trap (5B) and to the solenoid valve (5C)
-
Check multi-function display
-
Turn on the water. Do not darken the room.
-
Install the urinal to cover the daylight sensor (figure 7)
-
Three minutes after completing the installation there will be a flush of approx. 10 seconds so that
the siphon trap is filled with water
-
After a break of 8 seconds there will be another flush of approx. 2 seconds
-
The urinal can then be used
Fault
No flush
Flush, low
Flush, constant
Flushing every 60 sec. Stadium mode
Residual water does
not flow off
info@hygiene-shop.eu - www.hygiene-shop.eu
Cause
Water supply interrupted
Flow limiter blocked*
Solenoid valve damaged
Cable connections interrupted
Battery empty
Power supply interrupted
Cleaning session
Water supply reduced
Flow limiter blocked*
Solenoid valve damaged
Low water pressure
Solenoid valve damaged
Siphon trap or drains blocked
11
Solution
Open shut-off or preliminary shut-
off device
Clean*
Replace valve block
Establish connections
Replace
Ensure power supply
Automatically latest after 30
minutes
Open shut-off or preliminary shut-
off device
Clean*
Replace valve block
Flush volume increase (page 11.1)
Replace valve block
Automatic switchover
Replace or rectify