Product Description; Unit Variants; System Components - AEREX geniovent.x 600 F Notice De Montage Et Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and operating instructions for geniovent.x 600 - 900 F
Notice de montage et mode d'emploi geniovent.x 600 - 900 F
Supp
ly air
Exha
ust
air
Fig. 1: Ventilation and air extraction, schematic dia-
gram, geniovent.x 900 F R.
1
Exhaust air grille
2
Heat exchanger
3
Outgoing air fan
4
Outside air fan
5
Exhaust air filter
6
Outside air filter
7
Bypass shutter

5.2 Product description

• Decentralised heat recovery unit with air@home con-
trol.
• Integrated Ethernet interface for linking to networks and
for operational monitoring and control via the free
air@home app (Android / iOS) or www.air-home.de web
tool.
• Integrated USB-B socket for configuring the geniovent.x
unit using free commissioning software on a laptop / PC.
• CO2 sensor for demand-driven ventilation integrated as
standard.
• Low energy consumption thanks to 3-D impellers that
are bent backwards. Degree of heat provision up to 95
%.
• Fans, with particularly energy-saving DC motors.
• Supply air and exhaust air volumes for ventilation levels
1, 2 and 3 can be set separately. Air volumes can be set
in continuously variable manner.
• Volumetric flow ranges of 150...560 m³/h and 200...830
m³/h.
• The highest permitted resistance in the channel system
at maximum ventilation power is 50 Pa. Increased resist-
ance in the channel system reduces the ventilation
power.
• The unit covers should be opened with a tool.
EN
Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de
• Simple filter replacement, filter is freely accessible once
the covers have been opened. Pollen filter of filter class
ePM1 55% (F7) in the outside air and air filter of filter
Outgoin
g air
class ePM 10 60% (M5) in the exhaust air.
• Frost protection monitoring prevents the heat exchanger
from freezing at low outdoor temperatures.
Outside
• Cross-counterflow heat exchanger (variant G): For trans-
air
ferring exhaust air heat to the supply air.
• Enthalpy heat exchanger (variant E): In addition to heat,
the heat exchanger recovers some of the humidity from
the room.
• Bypass: Used to bypass the heat exchanger. On summer
nights, for example, slightly cooler air can be blown in.
• 2x DN 250 duct connections.
• All units with cross-counterflow heat exchanger (variant
G) are equipped with a condensate lift pump. The con-
nection diameter is 7 mm (inside), 10 mm (outside).
• RB-ZF4 control panel (item no. 0043.0570, included 1x in
the scope of delivery) with the functions: On/off, 4
levels, filter replacement and fault display.

5.3 Unit variants

geniovent.x 600, 900 Volumetric flow
F
Façade unit
L
R
G
E

5.4 System components

Outside and outgoing
air connection on left
Outside and outgoing
air connection on right
Cross-counterflow
heat exchanger
Enthalpy heat ex-
changer
SO
Supply air
at top
SU
Supply air
at bottom
SO-K
With
1a
Access to the exhaust air filter
ducts, sup-
1b
Access to the outside air filter and electrical ter-
ply air at
minal box
top (no
2
Unit cover
panels)
Function: To easily open and close the unit with
SU-K
With
a tool. Access to heat exchanger, condensate lift
ducts, sup-
pump, condensate tank* and heat register.
ply air at
3
RB-ZF4 control panel
bottom
Function: Control panel suited to the geniovent.x
(no pan-
ventilation unit. On/Off, 4 levels, filter replace-
els)
ment and fault display.
4
External CO2 sensor (optional) or external VOC
sensor (optional)
Function: CO2 sensor (optional): Sensor for regis-
tering carbon dioxide CO2.
5
Motion sensor (optional)
Function: for registering room occupancy.
6
Exhaust air filter, filter class ePM 10 60% (M5)
Function: Filters coarse dirt out of the exhaust
air.
7
Electrical terminal box with control circuit
board
Function: Central control unit of ventilation sys-
tem.
8
Outgoing air fan
Function: Conveys the used air to the outside.
9
Bypass
Function: Used to bypass the heat exchanger.
10
Heat exchanger
Function: In the heat exchanger, heat is trans-
ferred between the exhaust air and supply air
flows.
11
Outside air fan
Function: Conveys fresh air into the living area.
12
Outside air filter, filter class ePM1 55% (F7)
Function: Filters the finest contamination, e.g.
pollen, out of the outside air.
13
Condensate tank*
Function: Condensate collects in the stainless
steel condensate tank.
14
Condensate lift pump*
Function: Pumps the collected condensate out of
the ventilation unit (hose in outgoing air socket).
15
Outside air, outgoing air shutters
Function: To close off the unit when stationary.
7185.1235.0003_RLF.9_02.23_AS
2