Overview
The WEBCARDLX, WEBCARDLXE or WEBCARDLXMINI allows users to operate any
compatible Tripp Lite UPS System or network-enabled PDU as a managed device on
the network, accessible via Web browser, Network Management Station or telnet/SSH.
This manual refers to installing the card in a UPS system, but the same instructions
apply to installing the card in a compatible PDU.
Features
A
Ethernet Port: RJ45 jack connects the WEBCARDLX, WEBCARDLXE or
WEBCARDLXMINI to the network using a standard Ethernet patch cable. The Link
LED
A1
and Status LED
table on page 3.
Micro-USB Port: Use this port to directly connect with a computer running a
B
terminal emulation program. A cable (part number 73156A) is included with the
WEBCARDLX, WEBCARDLXE or WEBCARDLXMINI. If you need to order a
replacement cable, contact Tripp Lite Customer Support at 773.869.1234.
Type-A USB Port: Use this port to connect a Tripp Lite ENVIROSENSE 2 module
C
(E2MT, E2MTDO, E2MTDI, E2MTHDI) for a variety of environmental monitoring and
control options. See tripplite.com for more information about these modules.
Note: Do not connect a keyboard or mouse to this port.
Reset Button: The reset button is recessed, accessible through a small hole
D
under the RJ45 network port. Use a paper clip or other suitable object to press the
reset button for 3 seconds to reboot the network interface. Rebooting the network
interface will not erase network settings or interrupt AC power. Press and hold the
reset button for 20 seconds to restore the network interface to its factory default
settings. Restoring to the factory default will erase all previously saved data—
including network settings—without interrupting AC power.
E
Status LED: Shows WEBCARDLX, WEBCARDLXE or WEBCARDLXMINI status. See
the table on page 3 for a description of LED behavior.
A2
indicate the operating conditions, as shown in the
2