Installation
Read this installation manual completely to ensure proper installation, then file it
Installation
with the owner or maintenance department. Compliance and conformity to drain
requirements and other local codes and ordinances is the responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted for before
Packing List
discarding any packaging material.
IS
T H
E
S ID
U P
Flush the water supply lines before beginning installation and after installation is
complete. Test the unit for leaks and adequate water flow. Main water supply to the
eyewash should be "ON" at all times. Provisions shall be made to prevent unauthorized
shutoff.
The ANSI Z358.1 standard requires an uninterrupted supply of flushing fluid. Bradley
plumbed emergency fixtures require a minimum of 30 PSI (0.21 MPa) flowing pressure.
Flushing fuid should be tepid per ANSI Z358.1.
Self-closing spring-loaded valves are not UL classified to ANSI Z358.1.
The inspection and testing results of this equipment should be recorded weekly to verify
proper operation. This equipment should be inspected annually to ensure compliance
with ANSI Z358.1.
Workers who may come in contact with potentially hazardous materials should be
trained regarding the placement and proper operation of emergency equipment per ANSI
Z358.1.
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA
TEL: 1-800-BRADLEY
FAX: (262-251-5817)
http://www.bradleycorp.com
114-051
For questions regarding the operation or installation of this product, visit www.
bradleycorp.com or call 800-BRADLEY (272.3539).
Product warranties and parts information may also be found under "Products" on our
web site at bradleycorp.com.
NOTICE! Avoid cleaners containing organic solvents, alcohols, and hydrocarbons. Rinse with water
after cleaning.
Supplies Required:
¼" anchors and bolts
Teflon tape and pipe sealant
Piping to ½"
Piping to 1¼"
sign-mounting hardware
Local codes may require the installation of a backflow prevention valve to complete proper installation.
Compliance with local codes is the responsibility of the installer. Valve must be tested annually to verify that it
is functioning properly. Backflow prevention valves are not included with the fixture and may be supplied by the
contractor or purchased from Bradley Corporation.