2. Circuit is not used to supply any other electrical needs
(lights, appliances, etc.)
3. Extension cords comply with a 15 amp circuit breaker
or 15 amp time delay fuse.
4. Circuit is equipped with a 15 amp circuit breaker or
15 amp time delay fuse.
If any of the above conditions cannot be met, or if opera-
tion of the compressor repeatedly causes interruption of
power, it may be necessary to operate it from a 20 amp
circuit. It is not necessary to change the cord set.
Extension Cords
It is preferable to use extra air hose instead of an exten-
sion cord to avoid voltage drop and power loss to the
motor, and to prevent overheating.
If an extension cord must be used, be sure it is:
• 12 gauge (AWG) or heavier. (Wire size increases as
gauge number decreases. 10 AWG and 8 AWG
may also be used. DO NOT USE 14 OR 16 AWG.)
• a three-wire extension cord that has a three-connec
tor grounding plug, and a three-slot receptacle that
will accept the plug.
• no longer than 50 feet
• in good condition
1. Before attaching air hose or accessories, make
sure the "AUTO/O" lever is set to "O" and the air
regulator is closed.
2. Attach hose and accessories.
TOO MUCH AIR PRESSURE CREATES A
HAZARDOUS RISK OF BURSTING. CARE-FULLY
FOLLOW STEPS 3 AND 5 BELOW EACH TIME
THE COMPRESSOR IS USED.
Compressed air from the outfit may contain water
condensation. Do not spray unfiltered air at an
item that could be damaged. Some air operated
tools or devices may require filtered air. Read the
instructions for the air tool or device.
3. Check the manufacturer's maximum pressure rating
for air tools and accessories. The regulator outlet
pressure must never exceed the maximum
pressure rating.
4. Turn the "AUTO/O" lever to "AUTO" and allow tank
pressure to build. Motor will stop when tank
pressure reaches "cut-out" pressure.
5. Open the regulator by turning it clockwise. Adjust
the regulator to the correct pressure setting. Your
compressor is ready for use.
Break-in Procedure
This procedure is required only once, before the air com-
pressor is put into service.
1. Set the pressure switch "AUTO/O" lever in the
2. Plug the power cord into the correct branch circuit
3. Do not attach hose to outlet. Leave the outlet open
4. Turn the regulator clockwise, opening it fully, to
5. Move the "AUTO/O" lever to "AUTO". The com-
6. RUN THE COMPRESSOR FOR 15 MINUTES.
7. After 15 minutes, close the regulator by turning it
OPERATING PROCEDURES
6. Always operate the air compressor in well-
WHEN YOU ARE FINISHED:
7. Set the "AUTO/O" lever to "O".
8. Turn the regulator counterclockwise and set the
9. Remove the air tool or accessory.
10. Open the regulator and allow the air to slowly
11. Drain water from air tank.
12. After the water has been drained, close the drain
9 ENG
Serious damage may result if the following
break-in instructions are not closely fol-
lowed.
"O" position for "Off".
receptacle.
to the atmosphere.
prevent air pressure build-up in the tank.
pressor will start.
Make sure the regulator is open and there is no tank
pressure build-up.
counterclockwise. The air tank will fill to cut-out
pressure and then the motor will stop.
ventilated areas; free of gasoline or other solvent
vapors. Do not operate the compressor near the
spray area.
outlet pressure to zero.
bleed from the tank. Close the regulator when
tank pressure is approximately 20 psi.
WATER WILL CONDENSE IN THE AIR TANK. IF
NOT DRAINED, WATER WILL CORRODE AND
WEAKEN THE AIR TANK CAUSING A RISK OF
AIR TANK RUPTURE.
NOTE:
If drain cock valve is plugged, release all air
pressure. The valve can then be removed,
cleaned, then reinstalled.
valve. The air compressor can now be stored.
D20015 Rev. 1 6/28/00