charge opening of the safety valve without obstructions.
3. Mount the product at the highest point of the heat generator or in its imme-
diate vicinity at the flow line.
- A connection line with a maximum length of 1 m and the size of the inlet
cross section may be installed between the product and the heat gen-
erator.
4. Mount the product with the insulation.
5.3
Mounting the discharge line
BURNS CAUSED BY HOT LIQUID
Water in heating systems is under high pressure and can have temperatures of
more than 100 °C.
Verify that the discharge line is installed in such a way that blown off liquid
cannot cause injury or damage.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
 Verify that the discharge line is accessible and easy to oversee.
 Verify that the drain line of the funnel has twice the cross section of the
inlet of the safety valve.
1. The discharge line must have a gradient; its cross section must have at
least the same cross section as that of the discharge opening.
- The length of the discharge line must not exceed 2 m; the maximum
number of elbows is 2. If these values (2 elbows, 2 m line length) are
exceeded, the diameter next in size must be used for the discharge line
with a maximum of 3 elbows and a maximum line length of 4 m.
2. Drain the liquid discharged via the discharge line into a drain outlet or a
container that can hold the total capacity of the system.
Mounting
WARNING
KSG Magnum
EN
11