Overheating
The air curtain unit with electrical heating is
equipped with an overheat protection. If it is
deployed due to overheating, reset as follows:
1. Disconnect the power supply with the isolator
switch.
2. Determine the cause of overheating and
rectify the fault.
3. Open the service hatch. Locate the red button
next to the terminal box inside the air curtain.
The 2 and 2.5 metre/6.6 and 8.2 feet units are
equipped with two red buttons, one on the
outside of each terminal box.
4. Press the red button until a click is heard.
5. Reconnect the unit.
All motors are equipped with an integral
thermal safety cut-out. This will operate,
stopping the air curtain should the motor
temperature rise too high. The cut-out
will automatically reset when the motor
temperature has returned to within the motor's
operating limits.

Temperature control

Temperature control of SIRe maintains the
exhaust temperature. If the temperature
should exceed the preset value anyway
the overheating alarm goes off. For more
information see the manual for SIRe.

Fan replacement

1. Determine which of the fans is not
functioning.
2. Disconnect the cables from the relevant fan.
3. Remove the screws securing the fan and lift
the fan out.
4. Install the new fan as above in reverse order.
Replacing heating elements/heating
package (E)
1. Mark and disconnect the cables to the
heating elements/package.
2. Remove the mounting screws securing the
heating elements/package in the unit and lift
the heating elements/package out.
3. Install the new heating elements/package in
reverse order to the above.
24
AREC4000
Replacing the water coil (W)
1. Shut off the water supply to the unit.
2. Open the vent valve.
3. Open the drain valve.
4. When the water coil is empty, disconnect its
connections.
5. Remove the mounting screws securing the
coil in the unit and lift out.
6. Install the new coil in reverse order to the
above.
Draining the water coil (W)
The drain valve is on the underside of the coil
on the connector side. It can be accessed via
the service hatch.
Troubleshooting
If the fans are not working or do not blow proper-
ly, check the following:
• That the intake grille/filter is not dirty.
• Functions and settings of the SIRe control
system, see manual for SIRe.
If there is no heat, check the following:
• Functions and settings of the SIRe control
system, see manual for SIRe.
For units with electrical heating, also check the
following:
• Power supply to electric heater coil; check
fuses and circuit-breaker (if any).
• That the overheat protection has not been
deployed.
For units with a water coil, also check the follo-
wing:
• That the water coil is air free.
• That there is sufficient water flow and
pressure.
• That incoming water is heated adequately.
If the fault cannot be rectified, please contact a
qualified service technician.