RP973A PNEUMATIC AVERAGING RELAY
INPUT B1
INPUT A1
RP973
3
5
2
5
RP470B
3
2
VENT
.007 IN.
3
(TO DEAD ENDED DEVICE)
Fig. 5. Typical application using multiple
RP973 relays.
CAUTION
Equipment Damage Hazard.
Not recommended for averaging sensor lines.
For averaging sensor lines use the RP922A
Pneumatic Potentiometer.
Because input signal air flows from higher to lower, do
not use the RP973A on bleed-type thermostat lines. To
average bleed-type devices, use an isolating (repeating)
circuit. See Fig. 6. Refer to Fig. 7 for a typical application.
Automation and Control Solutions
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422
95-7253EF
J.H. Rev. 2-02
INPUT B2
INPUT A2
RP973
3
2
RP470B
2
3
M
VENT
.007 IN.
RP973
5
2
OUTPUT
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
.005 IN.
BLEED-TYPE
THERMOSTAT
5
.007 IN.
RESTRICTOR
5
1
RP470B LOCKOUT
RELAY PIPED AS
A REPEATER
1
RP470B RELAY ALLOWS THE USE OF AN AVERAGING
RELAY ON SMALL-NOZZEL BLEED DEVICES.
Fig. 6. RP973A in an isolating circuit.
THERMOSTAT
C6926
M
M
THERMOSTAT
M
M
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
M
.007 IN.
RESTRICTOR
5
2
3
EXH
B
RP973A
3
5
B
Fig. 7. Typical application.
customer.honeywell.com
INPUT 2
INPUT 1
5
3
RP973A
2
TO CONTROLLER
C4475
2
M7883

Publicité

Table des Matières
loading

Table des Matières