EMERGENCY LIGHTING PRODUCTS
ELPS502(M05) SYSTEM, ELPS502(M05) EXS/EXD SYSTEM,
ELPS50(M05) POWER SUPPLY, EVLA12 LIGHTING FIXTURE
Installation & Maintenance Information
APPLICATION
The ELPS502 model #M05 emergency lighting system is designed to automatically
provide illumination to designated areas during failure or interruption of power to the
normal lighting system. The ELPS502 is factory assembled and wired, and consists of one
ELPS50 power supply and two EVLA lighting fixtures.
When properly installed, the following raintight ELPS emergency lighting systems are UL
and cUL Listed for use in:
• ELPS50 Power Supply - Class I, Division 1, Groups B, C & D
• ELPS502 - Class I, Division 1, Groups B, C, D
Exit sign not UL/cUL
• ELPS502 (EXS/EXD) - Class I, Division 1 & 2, Groups C, D
(group B when ordered with GB suffix)
All ELPS emergency lighting systems are suitable for use in Class II, Division 1, Groups E,
F, G and simultaneous presence hazardous (classified) areas as defined by the National
Electrical Code®.
The ELPS50 power supply consists of a battery supply and battery recharging system
housed inside a hazardous area enclosure with all the circuitry to automatically turn on
emergency DC lighting fixture(s) when the normal power supply fails. A pilot light indicates
when normal power is being supplied to the unit. A "push-to-test" push button switch is
provided for periodic testing of the unit.
RATINGS
ELPS50 Power Supply:
Input
Output
Ambient Temp:
Lamp Fixtures:
Input
Ambient Temp.
Operating Temp. Code
NOTE: Ambient temperature at which ELPS50 power supply is rated is 0ºC to 40ºC to
maximize battery capacity. EVLA12 lighting fixtures are permitted in higher, 55ºC ambient
temperature areas for more freedom in selecting remote installation location.
National Electrical Code
is a registered Trademark of the National Fire Protection Association.
®
IF 1510 • 05/06
All manuals and user guides at all-guides.com
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
-120, 220/240 and 277 VAC ± 5%,
50 or 60Hz
-0.5 Amperes maximum
-12 VDC; 2.5 Amperes
-28 Watts for 1½ hours (ELPS502)
-29 Watts for 1½ hours (ELPS502 EXS/EXD)
-0ºC to 40ºC
EVLA12
ELPS EVI/ELPS EVA GB
-12 VDC
-12 VDC
-55ºC maximum
-40ºC maximum
-Class I - T4A;
-Class I - T4
-Class II, III - T3C
-Class II, III - T3C
-Simultaneous Presence - T3C
Copyright © 2006, Cooper Industries, Inc.
Detail indication logic is given below:
No Light
Steady Light (No blinks)
Light Blinks Once
• - •
Light Blinks Twice
• - • - •
Light Blinks Three Times
Immediately after supply power is initiated the indicating lamp will blink/pulse to indicate
that the unit is charging. Once installed with supply power, the ELPS requires 72 hours to
charge the battery. Once the unit has completed charging, the indicating light will stop
blinking and go to steady. Every six months, the unit will automatically perform a 90-
minute battery discharge test.
At the completion of the test, if it is determined not to have met the 90 minute
requirement, the indicating lamp will display circuit failure (3 blinks). At any time, if the
battery connection is not adequate the indicating lamp will display a battery failure (2
blinks).
The EVLA12 lighting fixture is a factory sealed assembly housing a single halogen
lamp/reflector light source. ELPS EVI and ELPS EVA GB Exit Signs are factory sealed
with a single incandescent light source. Lamps are included with all fixtures.
The EVLA12 is suitable for NEMA 4X locations when remote mounted (not installed on an
ELPS Power Supply) and supplied with a NEMA 4X breather/drain.
IMPORTANT
Emergency lighting system should be installed, inspected, operated, and maintained by
qualified and competent personnel.
To avoid personal injury, electric shock and equipment failure:
1. Do not use this equipment for other than intended use.
2. Do not use accessory equipment not recommended by the manufacturer.
3. Electrical power must be turned OFF before and during installation and
maintenance.
4. Equipment should be mounted in locations and at heights where it will not
readily be subjected to tampering by unauthorized personnel.
5. Do not mount near heat producing equipment.
6. In Class I areas, install and seal all equipment in accordance with the National
Electrical Code articles pertaining to Hazardous (Classified) Locations, plus any
other applicable codes.
7. Install only wiring systems with an equipment grounding conductor (which may
be the conduit system) to supply the ELPS.
8. two single-pole "Designated Disconnect" switches must be installed to
disconnect the battery circuit and the supply circuit for safety in maintenance
and servicing.
9. Free installation area of hazardous atmospheres before wiring.
10. Observe all battery handling precautions contained herein.
11. Hammers or prying tools must not be allowed to damage the flat joint surfaces
of the ELPS50 power supply housing. Do not handle covers roughly, or place
them on surfaces that might damage or scratch the flat joint surfaces.
12. To avoid shattering: Do not operate lamp in excess of rated voltage, protect
lamp against abrasion and scratches, and against liquids when lamp is
operating. Dispose of lamp properly.
IF 1510
AC power is removed from circuit
Fully Charged
Charging
Battery Failure
Circuit Failure
WARNING
Page 1

Publicité

Table des Matières
loading

Sommaire des Matières pour Cooper Crouse-Hinds ELPS502

  • Page 1 • - • Light Blinks Twice Battery Failure normal lighting system. The ELPS502 is factory assembled and wired, and consists of one • - • - • Light Blinks Three Times Circuit Failure ELPS50 power supply and two EVLA lighting fixtures.
  • Page 2 Figure 2. EVLA Lighting Fixture B. Attach and Adjust EVLA12 Lighting Fixture(s) NOTE: If installing ELPS502, fixtures are already attached. Proceed to Step 5 to adjust fixtures. CAUTION EVLA fixture head and arm are limited to no more than 180º of rotational adjustment.
  • Page 3 APPLICATIONS. (See Warning below) This Designated Disconnect Switch can be supplied as part of the ELPS502 emergency 2. Make all wiring connections following wiring diagram located on power supply battery light (Options S794 or Option S854).
  • Page 4: Complete Installation

    Unit needs to charge for 72 hours before conducting any tests. Do not disconnect AC power until unit is fully charged. 1. Attach the EVLA12 to a Cooper Crouse-Hinds EABC36 or EABL36 1" NPT outlet box. 2. Secure this assembly to the mounting surface with ¼ inch bolts or lag screws of the 3.
  • Page 5: Battery Replacement

    All manuals and user guides at all-guides.com BATTERY REPLACEMENT WARNING 1. Turn “designated disconnect” switch to “OFF”. To maintain explosionproof integrity, make sure all threads are fully engaged. 2. Remove ELPS50 power supply enclosure cover bolts and nuts, then lift off cover and carefully set it aside to prevent damage to the flat joint and flange gasket.
  • Page 6 IMPORTANT REMOVAL OF EXISTING CIRCUIT ASSEMBLY A DESIGNATED DISCONNECT SWITCH IS REQUIRED FOR SAFETY, TO (For units made BEFORE October, 2005). POWER THE ELPS502 EMERGENCY LIGHT SYSTEM AND CHARGE THE BATTERIES. 1. Disconnect branch AC power at circuit Figure 8 To avoid explosion, a Designated Disconnect switch with lock-in/lock-out breaker and lockout.
  • Page 7: Troubleshooting Guide

    All manuals and user guides at all-guides.com 8. Replace the old incandescent lamp (or old LED) in the pilot light and replace with the Assistance may also be obtained through your local Crouse-Hinds Sales Representative new, 2 volt LED supplied with the new interior assembly. or the Crouse-Hinds Service Center, P.O.
  • Page 8: Maintenance Record

    All manuals and user guides at all-guides.com MAINTENANCE RECORD NFPA 101 (2003) REQUIREMENTS " A FUNCTIONAL TEST SHALL BE CONDUCTED ON EVERY REQUIRED EMERGENCY EVLA EMERGENCY LIGHTING FIXTURE LIGHTING SYSTEM AT 30-DAY INTERVALS FOR A MINIMUM OF 30 SECONDS. AN ELPS EMERGENCY LIGHTING POWER SUPPLY ANNUAL TEST SHALL BE CONDUCTED FOR THE 1-1/2 HOUR DURATION.
  • Page 9: Produits D'éclairage De Sécurité

    L'enseigne de sortie n'est pas classifiée UL ou cUL • ELPS502 (EXS/EXD) - Class I, Division 1 & 2, groupes C et D durée de 90 minutes.
  • Page 10 B. Fixation et réglage du ou des luminaires EVLA12 Figure 2. Luminaire EVLA REMARQUE : les luminaires sont déjà fixés à l'appareil ELPS502. Poursuivre à l'étape 5 pour les régler. MISE EN GARDE Le réglage de la tête et du bras du luminaire EVLA est limité...
  • Page 11 Option S794 - interrupteur-sectionneur désigné à bascule en tant qu'élément du système le support de la pile du bloc d'alimentation. d'éclairage de sécurité ELPS502. Consulter l'étape 2b ci-dessous pour poursuivre le REMARQUE : il est possible de retirer le module interne pour faciliter le passage du câblage de l'alimentation.
  • Page 12: Essai Régulier

    All manuals and user guides at all-guides.com REMARQUE AVERTISSEMENT Dans les emplacements de classe I, classe II et présence simultanée de ces Pour éviter les décharges électriques, utiliser le luminaire uniquement avec des classes, limiter la visée ascendante du luminaire à un maximum de 30 degrés systèmes dotés d'un conducteur de mise à...
  • Page 13: Remplacement De La Pile

    All manuals and user guides at all-guides.com REMPLACEMENT DE LA PILE AVERTISSEMENT Pour maintenir l'intégrité de la caractéristique antidéflagrante, s'assurer que tous 1. Désactiver l'interrupteur-sectionneur désigné. les filets sont complètement vissés. 2. Retirer les boulons du couvercle et écrous du boîtier du bloc d'alimentation ELPS50 puis soulever le couvercle et le mettre soigneusement de côté...
  • Page 14: Trousse De Pièces De Rechange Pour Carte De Circuits Imprimés Et Pile

    ON EXIGE UN INTERRUPTEUR-SECTIONNEUR DÉSIGNÉ POUR PRÉSERVER LA SÉCURITÉ DE L'OPÉRATEUR, ALIMENTER LE SYSTÈME D'ÉCLAIRAGE DE AVANT octobre 2005). SÉCURITÉ ELPS502 ET CHARGER LES PILES. Figure 8 Pour empêcher une explosion, un interrupteur-sectionneur désigné avec fonction de 1. Couper l'alimentation secteur au niveau du verrouillage est requis pour effectuer des réparations de forme sécuritaire sur l'appareil...
  • Page 15: Retrait Du Module De Carte De Circuits Imprimés Existant

    All manuals and user guides at all-guides.com 8. Retirer l'ancienne ampoule incandescente (ou DEL) de la lampe témoin et la Il est aussi possible d'obtenir un soutien technique auprès de votre représentant régional remplacer par la DEL neuve de 2 volts fournie avec le module interne neuf. des ventes Crouse-Hinds ou du service après-vente à...
  • Page 16: Fiche D'entretien

    All manuals and user guides at all-guides.com FICHE D'ENTRETIEN SPÉCIFICATIONS DE LA NFPA 101 (2003) LUMINAIRE D'ÉCLAIRAGE DE SÉCURITÉ EVLA BLOC D'ALIMENTATION ELPS POUR ÉCLAIRAGE DE SÉCURITÉ " EFFECTUER UN ESSAI DE FONCTIONNALITÉ D'UN MINIMUM DE 30 SECONDES LUMINAIRE D'ÉCLAIRAGE DE SÉCURITÉ ELPS EVI (ENSEIGNE DE SORTIE) SUR TOUS LES SYSTÈMES D'ÉCLAIRAGE DE SÉCURITÉ...
  • Page 17 APLICACIÓN A continuación se explican las indicaciones: Luz apagada No existe energía AC en el circuito El sistema de iluminación de emergencia ELPS502 modelo #M05 está diseñado para iluminar • Luz constante (sin parpadear) Carga completa • La luz parpadea una vez Cargando determinadas áreas automáticamente en caso de falla o interrupción de la alimentación al...
  • Page 18 Figura 2. Accesorio de Iluminación EVLA B. Fije y ajuste el o los Accesorios de Iluminación EVLA12 NOTA: Si está instalando la unidad ELPS502, los accesorios ya se encuentran fijados. Siga al Paso 5 para ajustar los accesorios. PRECAUCIÓN La cabeza y el brazo del accesorio EVLA tienen un límite de 180º...
  • Page 19 Figura 4. Fuente de Alimentación ELPS50 - Vista interior Sección 501.15 del National Electrical Code y por otras normas aplicables. NOTA: Si está instalando la unidad ELPS502, la conexión de las puntas de NOTA: Refiérase al Paso 2b y asegúrese de que el sistema tiene instalada la caja alimentación de los accesorios de iluminación ya se encuentra lista.
  • Page 20: Complete La Instalación

    La unidad necesita cargarse durante 72 horas antes de realizar pruebas. No desconecte la energía AC hasta que la unidad esté cargada por completo. 1. Fije el EVLA12 a una caja de salida NPT de 1" Cooper Crouse-Hinds EABC36 o EABL36.
  • Page 21: Reemplazo De La Batería

    All manuals and user guides at all-guides.com REEMPLAZO DE LA BATERÍA PRECAUCIÓN 1. Configure el interruptor de desconexión designado en "OFF". Para mantener la integridad a prueba de explosiones, verifique que la lámpara esté completamente enroscada. 2. Retire los pernos y tuercas de la tapa del gabinete de la fuente de alimentación ELPS50, luego levante la tapa y retírela con cuidado a fin de evitar daños a la junta 8.
  • Page 22 SE REQUIERE UN INTERRUPTOR DE DESCONEXIÓN DESIGNADA POR MOTIVOS DE SEGURIDAD, PARA ALIMENTAR EL SISTEMA DE ILUMINACIÓN 1. Desconecte la energía ramal AC en el DE EMERGENCIA ELPS502 Y PARA CARGAR LAS BATERÍAS. interruptor y bloqueador del circuito. Figura 8 Para evitar explosiones, se requiere un interruptor de Desconexión Designada...
  • Page 23 All manuals and user guides at all-guides.com 8. Reemplace la lámpara incandescente (o LED) de la lámpara piloto con la LED nueva También puede obtener asistencia a través de su representante de ventas local Crouse- de 2 voltios suministrada con el ensamble del interior nuevo. Hinds o el centro de servicios de Crouse-Hinds, P.O.
  • Page 24: Registro De Mantenimiento

    All manuals and user guides at all-guides.com REGISTRO DE MANTENIMIENTO REQUISITOS NFPA 101 (2003) ACCESORIO DE ILUMINACIÓN DE EMERGENCIA EVLA "SE DEBE REALIZAR UNA PRUEBA FUNCIONAL SOBRE TODOS LOS SISTEMAS DE FUENTE DE ALIMENTACIÓN PARA ILUMINACIÓN DE EMERGENCIA ELPS ILUMINACIÓN DE EMERGENCIA REQUERIDOS, CADA 30 DÍAS Y DURANTE 30 ACCESORIO DE ILUMINACIÓN DE EMERGENCIA ELPS EVI (SEÑAL DE SALIDA) SEGUNDOS COMO MÍNIMO.