Connect the cable ends to the terminals of the switch.
•
Secure the magnet to the door. It must allow the door to close
and pass directly by the doorpost.
•
Secure the sensor to the doorpost so that when the door closes,
the sensor is aligned with the magnet. The maximum distance
between the parts of the door switch must be 0.2 in (5 mm) when
the door is closed.
TEMPERATURE SENSOR WITH OVERHEATING PROTECTION
•
Connect the cable to the temperature sensor's plug, see figure.
•
Screw the temperature sensor onto the wall, see figure.
•
The temperature sensor cannot be placed above the heater, it
must be at least 19.7 in (50 cm) away from it.
•
The temperature sensor must be 5.9-7.9 in (15-20 cm) from the
ceiling.
•
The temperature sensor must be at least 19.7 in (50 cm) from any
air opening (ventilation, door, window).
VAPORIZER
•
A vaporizer is connected to outputs SL and SN as shown in the
figure. If a vaporizer is connected, a vaporizer function must
also be selected from the control console settings. See User
instructions.
NB!
When connecting the control console with an electrical heater with
a vaporizer function ensure that the water tank is always filled with
water. When the water tank is empty, the vaporizer function is disabled
and there is a risk that the heating element may burn out.
CONNECTION OF A LIGHTING SYSTEM
•
Lighting/ventilation can be connected to the outputs LL and LN
of the control console as shown in the figure. In that case, it is