Check the settings
You can check your settings
by pressing
twice.
AKS 4100
COAX D22
280 mm
(0%) 4 mA
210 mm
060 mm
(100%) 20 mA
Press
to return to
default screen.
After running the quick set-up, go to the supervisor menu and change the following
parameters:
2.3.2 Blocking distance
2.3.3 Time constant
2.5.3 Epsilon R gas constant (Er gas)
Change to the value indicated for the temperature of the media. If a media range is giv-
en, choose the value of the lowest operating media temperature. See the List of Er gas
constant in .
2.5.7 Level threshold
4.1.1 Full area
4.1.2 Empty area.
The supervisor menu is protected by a passcode.
1.
Name the buttons on the AKS head 1-2-3-4 from left to right, see Fig. 30.
1 2 3 4
Fig. 30
Supervisor passcode = 1-2-3-4-1-2
2.
Press Arrow right (no. 1) once - the first digit 1 is marked, see Fig. 31.
Fig. 31
Mode d'emploi – ChillPAC et LP ChillPAC Mk 3
010823 fr 09/2022
67/79