General; Information About This Instructions Manual; Information About This Line Regulator - Linde R200 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 46
ENGLISH
INSTRUCTION FOR USE: 4-/6-PORT LINE REGULATOR
EN

1. GENERAL

1.1. INFORMATION ABOUT THIS INSTRUCTIONS MANUAL

This instruction is only intended for use with line regulator product type:
R200
R300
R500
Line regulators of this type are suitable to reduce a high supply pressure through diff erent pressure stages.
These regulators were assembled into piping system permanently.
These instructions enable you to operate the system safely and effi ciently. These instructions form an integral
part of the system and must always be kept with the system and within easy reach of staff at all times.
Prior to commencing any work, the staff must read these instructions carefully and understand the contents.
Observance of all the safety information and instructions for operation that are contained in these instructions
is essential to ensure work safety.
Local accident prevention regulations and general safety regulations governing the use of the system must
also be observed.
Illustrations in these instructions serve to ensure a basic understanding of the system and may diff er from
the actual version.

1.2. INFORMATION ABOUT THIS LINE REGULATOR

Line Regulators of this type are only suitable for gases defi ned as standard gas. The maximum working pres-
sure for line regulator is 300 bar.
Product Line
High Pressure Regulator
with
FKM
High Pressure Regulator with
EPDM
Relief Valve Seat
This table is not exhaustive. For questions and ambiguities please contact manufacturer.
Relief Valve Seat
(Purity 6.0 | brass chrome plated)
Suitable Gases
(including their mixtures):
High Purity
Inert
Flammable
Oxidizing
Use for O2
Not Suitable Gases
(including their mixtures):
Corrosive
Toxic
CO2, N2O
Suitable Gases
(including their mixtures):
High Purity
Inert
Flammable
Oxidizing
Use for CO2, N2O
Not Suitable Gases
(including their mixtures):
Corrosive
Toxic
O2
(share greater than 21%)
Hydrocarbons
4/298
(Purity 6.0 | stainless steel)
Suitable Gases
(including their mixtures):
High Purity
Inert
Flammable
O2 up to 200 bar
Corrosive (in doubt ask)
Toxic (in doubt ask)
Not Suitable Gases
(including their mixtures):
O2 above 200 bar and
share greater than 21%
CO2, N2O
NH3, SO2, H2S
Suitable Gases
(including their mixtures):
High Purity
Inert
Flammable
Oxidizing
Corrosive (in doubt ask)
Toxic (in doubt ask)
Use for CO2, N2O
Use for NH3, SO2, H2S
Not Suitable Gases
(including their mixtures):
O2
(share greater than 21%)
Hydrocarbons

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

R300R500

Table des Matières