Letter of compliance for ECO-design, Process & Comfort Chiller
Directive 2009/125/EC
Data:
High
<400kW
ChillPAC28V-A
229 kW
Sabroe unit
Legal limit
SEPR
9,30
7,0
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
+12/+7
High
<1500kW
ComPAC 151LV-A
932 kW
Sabroe unit
Legal limit
SEPR
8,02
8,0
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
+12/+7
High
<400kW
SABlight A400-1
392 kW
Sabroe unit
Legal limit
SEPR
5,02
5,0
Conditions
Evaporator
Condenser Inlet
Inlet/outlet
35
+12/+7
Reciprocating
<400kW
ChillPAC 28V-A
229 kW
Sabroe unit
Legal limit
Eta s,c
252
200
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
+12/+7
Screw, Air Cooled
<400kW
SABlight A340-1
324 kW
Sabroe unit
Legal limit
Eta s,c
161
161
Conditions
Condenser Inlet
Evaporator
35
+12/+7
See COMP1 calculations in the document named 'SEPR-SEER calculations' on
Calculation flow chart (COMP1SEPR/SEER-toolValidation)
Regulatory control:
www.ens.dk, www.sik.dk
Page 2 of 2
Process Chiller, Reciprocating water/brine cooled
Medium
<300kW
ChillPAC28V-C
113 kW
>400kW
Sabroe unit
Legal limit
SEPR
5,05
2,96
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
-2/-8
Process Chiller, Screw water/brine cooled
Medium
>300kW
ComPAC 151LV-A
514 kW
<1500kW
Sabroe unit
Legal limit
SEPR
4,60
3,93
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
-2/-8
Process Chiller water/brine evaporator, Air Cooled condenser
Medium
<300kW
A400-1EG
237
Sabroe unit
Legal limit
SEPR
3,73
2,32
Conditions
Evaporator
Condenser Inlet
Inlet/outlet
35
-2/-8
Comfort Chiller, water cooled
<1500kW
ChillPAC 112LV-A
1061 kW
<1500kW
Sabroe unit
Legal limit
Eta s,c
279
252
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
+12/+7
Comfort Chiller, water evaporator, Air cooled condenser
and www.rp-tuebingen.de
TPH/20-1-2021
High
ChillPAC 112LV-A
1061 kW
>300kW
Sabroe unit
Legal limit
SEPR
9,40
8,0
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
+12/+7
High
ComPAC 193LV-A
1455 kW
>300kW
Sabroe unit
Legal limit
SEPR
9,77
8,0
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
+12/+7
Screw
ComPAC151LV-A
927 kW
<1500kW
Sabroe unit
Legal limit
Eta s,c
254
252
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
+12/+7
Medium
ChillPAC 12LV-C
529 kW
Sabroe unit
Legal limit
SEPR
5,00
3,93
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
-2/-8
Medium
ComPAC 193LV-C
794 kW
Sabroe unit
Legal limit
SEPR
4,72
3,93
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
-2/-8
ComPAC 193LV-A
1455 kW
Sabroe unit
Legal limit
Eta s,c
265
252
Conditions
Condenser
Evaporator
Inlet/outlet
Inlet/outlet
30/35
+12/+7
www.sabroe.com