Change the following parameters in the same way: (AKS 4100 280 mm)
+ 2.3.2 Blocking distance from 50 mm to 0 mm
+ 2.3.3 Time constant from 5 sec. to 1 sec.
+ 2.5.7 Level threshold from 200 mm to 150 mm
+ 4.1.1 Full area - confirm or change to 0 mm. Passcode for level 4.x.x = 4-3-4-2-4-1
+ 4.1.2 Empty Area from 280 mm to 260 mm.
After the last change, press Return (no. 2) until "STORE NO" is displayed, see Fig. 35.
Fig. 35
Change to 'STORE YES' with Arrow down (no. 3) or Arrow up (no. 4) and Confirm (no. 2).
You will then return to the standard display and the AKS 4100 is now running with optimised
parameters.
Note: After changing the parameters, do NOT run a quick set-up. If you do so, you will need to
fill in the parameters again.
If you make a new set-up, please fill in the set-up parameters in Table 3 below, and add them
to your logbook.