White-Rodgers ALL-SPARK 50D50U-843 Directives D'installation page 3

Module non intégré d'allumage par étincelle directe 24 v
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Table 1: Configuration Menu Options
Menu Item
No.
System Ignition Type
1. IP system menu will be displayed if System Ignition Type is selected as IP
Tries for Ignition
Trial for Ignition
(TFI) Timing
Pre-purge
Inter-purge
Flame Sense Type
Auto Restart Time
Reset to Default
2. DS system menu will be displayed if System Ignition Type is selected as DS
Tries for Ignition
Trial for Ignition
Timing
Pre-purge
Inter-purge
Post-purge
Flame Sense Type
Auto Restart Time
Inducer/Pressure
Switch Option
Enable
Reset to Default
LED 1
LEDs 2 & 3
(flash)
Display
1.0
S-Y-S
IP
IP*, dS
C C * (continuous),
1.1
t-r-Y
1, 2, 3
1.2
I-g-n
90
90*, 4,15, 30, 60
1.3
0 0 *,15, 30, 45
P-r-E
1.4
0 0 *,15, 30, 45
I-n-t
1.5
F-L-S
LL*, rE
LL
1.6
5 5 *, 60
A-u-t
1.7
C-F-d
No*, Ys
No
2.1
1 1 *, 2, 3
t-r-Y
4 4 *, 7,10,11,15,
2.2
I-g-n
21
2.3
P-r-E
30*, 45, 0,15
30
2.4
I-n-t
30
30*, 45, 90, 0,15
2.5
0 0 *, 5,15, 30
P-S-t
2.6
F-L-S
LL
LL*, rE
2.7
5 5 *, 60
A-u-t
2.8
I-n-d
OF*, On
OF
2.9
C-F-d
No*, Ys
No
Unit
Description / Rule
N/A
Intermittent Pilot (IP) or Direct Spark (DS)
Number of times the control will retry ignition
N/A
before going to auto restart delay.
Seconds
The time the control will spark for each try
Seconds
Delay time before spark ignition attempt
Seconds
Delay time in-between spark attempts
N/A
Local (LL) or Remote (rE) flame sense.
Delay time after control reports Gas Valve Off
Minutes
Lockout or No Flame During TFI Error.
Control resets and goes back to standby.
Reset to factory default for IP system
N/A
configuration choices
Number of times the control will retry ignition
N/A
before going to auto restart delay.
Seconds
The time the control will spark for each try
Seconds
Delay time before spark ignition attempt
If 2 or 3 tries for ignition are selected, 0 seconds
Seconds
inter-purge will not be available
Seconds
Delay time after heat call has ended
N/A
Local (LL) or Remote (rE) flame sense
Delay time after control reports Gas Valve Off
Minutes
Lockout or No Flame During TFI Error.
Control resets and goes back to standby.
If control being replaced has inducer/pressure
N/A
switch option, enable this setting to ON
Reset to factory default for DS system
N/A
configuration choices
* Factory Default Setting
3