• 50M56D-751 Integrated Furnace Control
• 2 – 1/2" Sheet Metal Screws
50M56D-751 is an aftermarket direct replacement
control kit for Carrier single stage furnace products with
PSC blower motors.
ELECTRICAL RATINGS:
Input Low Voltage: 24 VAC, 60 Hz
Input Line Voltage: 120 VAC, 60 Hz, 1φ
Max Input Current: 0.45 A @ 24 VAC
Relay Contact Ratings:
Gas Valve: 1.5 A, 0.6 PF @ 24 VAC
Ignitor Relay: 1.2 A @ 120 VAC
Inducer Relay: 2.8 A @ 120 VAC
Circulator Relay: 10 FLA, 25 LRA @ 120 VAC
Humidifier Load: 1.0 A @ 24 or 120 VAC
Electronic Air Cleaner: 1.0 A @ 120 VAC
Flame Current Requirements:
Minimum current to ensure flame detection:
0.25 μA DC*
Maximum current for non-detection: 0.1 μA DC
Maximum allowable leakage resistance:
100 M ohms
* Measured with a DC ammeter
Flame Establishing Time: 0.8 seconds maximum
Flame Failure Response Time: 2.0 seconds
maximum
OPERATING TEMPERATURE RANGE:
-40° to 176°F (-40° to 80°C)
HUMIDITY RANGE:
5 to 95% relative humidity (non-condensing)
emerson.com/white-rodgers
50M56D-751
Carrier Integrated Single Stage
120V Hot Surface Ignition Control Kit
INSTALLATION INSTRUCTIONS
• Installation Instructions
TWINNING: 50M56D-751 can be twinned. The other
control must also be a 50M56D-751 to ensure
proper functionality.
SPECIFICATIONS & TIMINGS
AGENCY APPROVALS:
GASES APPROVED:
Natural, Manufactured, Mixed,
Liquid Petroleum, and LP Gas Air Mixtures.
CAUTION
!
Risk of Electric Shock.
Disconnect electric power
to system until installation
is complete. Do not use on
circuit exceeding specified
voltage. Higher voltage will
damage control and could
cause shock or fire hazard.