KMT-01
VOLTAGE AND CONTINUITY TESTER
Operation
1.Function test / Self test
1. Test the voltage tester on a known source.
2. The "!" LED will light on when there is a voltage over 50V, even if the battery is low or if the battery has been removed.
3. Warning: To avoid electric shock, disconnect the test leads from any source of voltage before turn on the self-check test
function.
4. When press "Autotest" button, all voltage LEDs (4) will must be light on, and
The continuity test's LED (9) will light on, buzzer sound. This shows the tester self-test was done.

2.Voltage Test

1. Connect both test probes with power source.
2. As from a voltage of >12V the voltage tester switches on automatically.
3.The voltage is displayed via LEDs.
4. For AC voltages the "AC" LED is illuminated .
5. For DC voltages the "-DC or +DC" LED is illuminated.
6. The instruments are equipped with an LED row comprising: ±12,24,36,50, 120,400,690 For DC voltage; 12, 24, 36, 50,
120, 400 for AC voltage. the polarity of the voltage displayed refers to the instrument test probe (+).
7. Due to technical reasons the instrument cannot effectuate an automatic switch-on for DC voltages within the range of
approx. 0V to –/+8V.