FK06 DIALSET®
• Spring bonnet with setting knob and scale
• Adjustment spring
• Fine filter in clear filter bowl
• Ball valve
OPTIONS
FK06-...DUT = with clear filter bowl, threaded union
connectors, filter mesh size 50 μm
FK06-...DUS = with clear filter bowl, sweat union
connectors, filter mesh size 50 μm
ASSEMBLY
Installations Guidelines
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in these instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
It is necessary during installation to follow the installation
instructions, to comply with local requirements and to
follow the codes of good practice.
• Install in horizontal pipework with filter bowl
downwards
—
This position ensures optimum filter efficiency
• Install shutoff valves
• Ensure good access
—
Degree of contamination can be easily seen with
clear filter bowl
—
Simplifies maintenance and inspection
• The installation location should be protected against
frost.
Assembly Instructions
It is recommended to install an inlet non-return valve.
IMPORTANT
When using soldering connections, do not solder
the connections together with the filter combina-
tion. High temperature will irreparably damage
important internal working components.
1. Thoroughly flush pipework.
2. Fit filter combination.
• Note flow direction (indicated by arrow).
• Install without tension or bending stresses.
3. Set outlet pressure.
38-00059EFS—01
Drain for rinse water
The rinse water must be piped to the drain in such a way
that no back pressure can occur.
1. Discharge into drain connector.
2. Discharge into floor drain.
Fig. 1. Drain for rinse water.
Table 1. Rinsing Quantity.
Filter size
3/4"–1 1/4"... 101-103 6.6 gallons (25 liters)
* at 58 psi (4 bar) inlet pressure and a rinse duration of 15
seconds
COMMISSIONING
Setting outlet press
Changing the Downstream Pressure
(See Fig. 2)
Remove the dust cap from the FK06. The FK06 is factory
set to 60 psi.
To adjust the outlet pressure to a desired setting:
1. Loosen the locking screw by turning counter-
clockwise
2. Turn the adjusting knob counter-clockwise
reduce pressure or clockwise
sure.
3. Lock the setting by turning the locking screw clock-
wise
.
4. Replace the dust cap over the dial.
2
C
M36609
Rinsing quantity*
(Do not remove this screw.)
to increase pres-
C in in.
(mm)
3/4 (20)
to