TEMPERATURES MENU

OPERATING SET POINT
User adjustable setting 90°F to 190°F range; factory default is
120°F. When the water temperature sensed by the control system
from the immersion Temperature Probe reaches the Operating
Set Point the control system will end the heating cycle. A call for
heat will be activated again when the water temperature drops
below the Operating Set Point minus the 1st Differential Setting.
Example: Operating Set Point is 120°F, the 1st Differential Setting
is 2°F. A call for heat will be activated when the sensed water
temperature drops to 118°F.
DIFFERENTIAL SETTINGS
Adjustable user setting(s) 1°F to 20° range; factory default is 9°F.
The water heaters covered in this manual will have between 1 and
5 heating elements. There is at least one Differential Setting on
all models. There will be additional Differential Settings for each
additional heating element installed.

OPERATING SEQUENCE

On a water heater equipped with 3 heating elements, with an
Operating Set Point of 120°F and all Differential settings at 2°F
the On/Off sequencing of heating elements would be as follows:
Table 9. On/Off Element Sequencing in 3-Element Water Heater
ELEMENT
DIFFERENTIAL
NUMBER
SETTING
Element 1
2°F
Element 2
2°F
Element 3
2°F
TANK TEMPERATURE
Non adjustable information display. Current water temperature as
sensed by the control system from the immersion Temperature
Probe.
TANK PROBE OFFSET
User adjustable setting -5°F to +5°F range; factory default is 0°F.
If the current Tank Temperature is sensed (from the immersion
Temperature Probe) at 120°F and the offset is adjusted to -5°F the
control system would calibrate or "offset" the Tank Temperature to
115°F. Heating cycles would then start/stop based on the calibrated
Tank Temperature.
Used to calibrate for slight differences in control system temperature
sensing. This can improve the precision of temperature control
in the storage tank and at points of use. This feature can also be
used to compensate for building recirculation loops (hot water
returning to the storage tank) that may cause the heating cycle
to terminate prematurely.
21
TURN ON TEMP
TURN OFF TEMP
118°F
120°F
116°F
118°F
114°F
116°F