15 Données spécifiques DeviceNet
Class
Inst.
Attr.
Fh
3h
1h
Fh
4h
1h
Fh
5h
1h
Fh
6h
1h
Fh
7h
1h
Fh
8h
1h
Fh
9h
1h
Fh
Ah
1h
Fh
Bh
1h
Fh
Ch
1h
Fh
Fh
1h
Fh
10h
1h
Fh
11h
1h
Fh
12h
1h
Fh
13h
1h
Fh
14h
1h
Fh
15h
1h
Fh
16h
1h
GEMÜ 1242
Paramètres
Function of high visibility
On site programming
Switch Point OPEN request
Switch Point OPEN real
Switch Point CLOSED request
Switch Point CLOSED real
Alarm stroke reduction OPEN
Alarm stroke reduction
CLOSED
Alarm opening time
Alarm closing time
Programmed position OPEN
Programmed position CLOSED 2 octets UINT
Programmed stroke
Last position OPEN
Last position CLOSED
Last stroke
Valve position
Sensor error
Lon-
Type de
Accès
gueur
données
1 byte
USINT
Get/Set 3
1 byte
Boolean Get/Set 0
1 byte
USINT
Get/Set 25
1 byte
USINT
Get
1 byte
USINT
Get/Set 12
1 byte
USINT
Get
1 byte
USINT
Get/Set 1
1 byte
USINT
Get/Set 1
1 byte
USINT
Get/Set 0
1 byte
USINT
Get/Set 0
2 octets UINT
Get
Get
2 octets UINT
Get
2 octets UINT
Get
2 octets UINT
Get
2 octets UINT
Get
2 octets UINT
Get
1 byte
USINT
Get
36 / 43
Valeur
Plage de valeurs
par dé-
faut
0 = OFF
1 = 33 %
2 = 66 %
3 = 100 %
4 = Closed 100 % ; Open OFF
5 = Closed OFF ; Open 100 %
0 = enabled
1 = disabled
3 % – 97 %
0
Affichage des valeurs 0 % –
100 %
3 % – 97 %
0
Affichage des valeurs 0 % –
100 %
0 = disabled
1 = 25 %
2 = 50 %
3 = 75 %
0 = disabled
1 = 25 %
2 = 50 %
3 = 75 %
0 – 255 (0 = éteint)
0 – 255 (0 = éteint)
0
Affichage de valeurs numé-
riques
0 - 4092
0
Affichage de valeurs numé-
riques
0 - 4092
0
Affichage de valeurs numé-
riques
0 - 4092
0
Affichage de valeurs numé-
riques
0 - 4092
0
Affichage de valeurs numé-
riques
0 - 4092
0
Affichage de valeurs numé-
riques
0 - 4092
0
Affichage de valeurs numé-
riques
0 - 4092
0
0 = Sensor OK
1 = Sensor error position closed
2 = Sensor error position open
www.gemu-group.com