6.ANNEXE
6. ANNEXE
6.1 Spécification du câble
(1) Appareil monophasé
Courant maximal
Ligne de
de la plaque
signalétique
Pas plus de
2×1.5mm
10A
10~16A
2×2.5mm
16~25A
2×4mm
25~32A
2×6mm
32~40A
2×10mm
40 ~63A
2×16mm
63~75A
2×25mm
75~101A
2×25mm
101~123A
2×35mm
123~148A
2×50mm
148~186A
2×70mm
186~224A
2×95mm
(2) Appareil triphasé
Courant maximal
Line de
de la plaque
phase
signalétique
Pas plus de 10A 3×1.5mm
10~16A
3×2.5mm
16~25A
3×4mm
25~32A
3×6mm
32~40A
3×10mm
40 ~63A
3×16mm
63~75A
3×25mm
75~101A
3×25mm
101~123A
3×35mm
123~148A
3×50mm
148~186A
3×70mm
186~224A
3×95mm
Lorsque l'appareil sera installée à l'extérieur, veuillez utiliser des câbles pouvant résister aux
UV(rayons ultra-violet).
Line de terre
phase
2
1.5mm
2
2
2
2.5mm
2
2
4mm
2
2
6mm
2
2
10mm
2
2
16mm
2
25mm
2
2
2
25mm
2
2
35mm
2
2
50mm
2
2
70mm
2
2
95mm
Line de terre
2
2
1.5mm
2
2
2.5mm
2
2
4mm
2
2
6mm
2
10mm
2
2
2
16mm
2
2
25mm
2
2
25mm
2
2
35mm
2
2
50mm
2
70mm
2
2
2
95mm
MCB
Protection contre le fluage
20A
30mA moins de 0.1 sec
32A
30mA moins de 0.1 sec
40A
30mA moins de 0.1 sec
40A
30mA moins de 0.1 sec
63A
30mA moins de 0.1 sec
80A
30mA moins de 0.1 sec
100A
30mA moins de 0.1 sec
125A
30mA moins de 0.1 sec
160A
30mA moins de 0.1 sec
225A
30mA moins de 0.1 sec
250A
30mA moins de 0.1 sec
280A
30mA moins de 0.1 sec
Protection contre le
MCB
fluage
20A
30mA moins de 0.1 sec
32A
30mA moins de 0.1 sec
40A
30mA moins de 0.1 sec
40A
30mA moins de 0.1 sec
63A
30mA moins de 0.1 sec
80A
30mA moins de 0.1 sec
100A
30mA moins de 0.1 sec
125A
30mA moins de 0.1 sec
160A
30mA moins de 0.1 sec
225A
30mA moins de 0.1 sec
250A
30mA moins de 0.1 sec
280A
30mA moins de 0.1 sec
44
Ligne de
signalisation
n×0.5mm
2
Ligne de
signalisation
2
n×0.5mm