• Características técnicas
Accuracy
Exactidão na energia activa:
Exactidão na energia reactiva:
Marcação CE
The F3N300 product complies with:
•
The requirements of the European directive on electromagnetic compatibility (EMC) no. 89/336/CEE dated 3 May
1989, modified by directive no. 92/31/CEE dated 28 April 1992 and by directive no. 93/68/CEE dated 22 July 1993.
•
Low voltage directive no. 73/23/CEE dated 19 February 1973, modified by directive no. 93/68/CEE dated 22 July
1993, modified by directive n° 2006/95/CE.
Compatibilidade electromagnética
Immunity to electrostatic discharges:
Immunity to radiated radio-frequency fields:
Immunity to electrical fast transients/bursts:
Immunity to surge immunity:
Immunity to conducted disturbances:
Immunity to power frequency magnetic fields:
Conducted and radiated emissions:
Immunity to voltage dips and short interruptions:
Clima
Operating-temperature range:
Storage temperature range:
Humidity:
Salt mist:
Características mecânicas
Vibration from 10 to 50 Hz:
Isolação
Installation category:
Degree of pollution:
Rated impulse withstand voltage:
Front face:
Electric safety:
Características dos PMD
Tipo de características
Função (eventual) de avaliação da qualidade da alimentação
Classificação dos PMD
Temperatura
Humidade + Altitude
Classe de desempenho de funcionamento da potência activa
ou da energia activa (se a função estiver disponível)
46
IEC 62053-22, Class 0,5S
IEC 62053-23, Class 2
IEC 61000-4-2 - Level III
IEC 61000-4-3 - Level III
IEC 61000-4-4 - Level III
IEC 61000-4-5 - Level III
IEC 61000-4-6 - Level III
IEC 61000-4-8 - Level III
CISPR11 - Class A
IEC 61000-4-11
IEC 60068-2-1/IEC 60068-2-2
-10 °C to +55 °C
IEC 60068-2-1/IEC 60068-2-2
-20 °C to +85 °C
IEC 60068-2-30 - 95 %
IEC 60068-2-52 - 2,5 % NaCl
IEC 60068-2-6 - 2 g
III (480 VAC ph /ph)
2
IEC 60947-1 - V imp: 4 kV
Class II
IEC 61010-1
Conformidade IEC 61557-12 Edition 1 (08/2007)
Exemplos de valores
característicos possíveis
-
SD
K55
-
0,5
Outras características
complementares
-
-
-
-
-