Accuracy
Accuracy on active energy:
Accuracy on reactive energy:
CE Marking
The F3N300 product complies with:
•
The requirements of the European directive on electromagnetic compatibility (EMC) no. 89/336/CEE dated 3 May
1989, modified by directive no. 92/31/CEE dated 28 April 1992 and by directive no. 93/68/CEE dated 22 July 1993.
•
Low voltage directive no. 73/23/CEE dated 19 February 1973, modified by directive no. 93/68/CEE dated 22 July
1993, modified by directive n° 2006/95/CE.
Electromagnetic compatibility
Immunity to electrostatic discharges:
Immunity to radiated radio-frequency fields:
Immunity to electrical fast transients/bursts:
Immunity to surge immunity:
Immunity to conducted disturbances:
Immunity to power frequency magnetic fields:
Conducted and radiated emissions:
Immunity to voltage dips and short interruptions:
Climate
Operating-temperature range:
Storage temperature range:
Humidity:
Saling fog:
Mechanical characteristics
Vibration from 10 to 50 Hz:
Insulation
Installation category:
Degree of pollution:
Rated impulse withstand voltage:
Front face:
Electric safety:
Characteristics of PMD
Type of characteristic
Power quality assessment function (if any)
Classification of PMD according to 4.3
Temperature
Humidity + Altitude
Active power or active energy function (if function available)
performance class
IEC 62053-22 class 0.5S
IEC 62053-23 class 2
IEC 61000-4-2 - Level III
IEC 61000-4-3 - Level III
IEC 61000-4-4 - Level III
IEC 61000-4-5 - Level III
IEC 61000-4-6 - Level III
IEC 61000-4-8 - Level III
CISPR11 - Class A
IEC 61000-4-11
IEC 60068-2-1/IEC 60068-2-2
-10 °C to +55 °C
IEC 60068-2-1/IEC 60068-2-2
-20 °C to +85 °C
IEC 60068-2-30 - 95 %
IEC 60068-2-52 - 2,5 % NaCl
IEC 60068-2-6 - 2 g
III (480 VAC ph /ph)
2
IEC 60947-1 - V imp: 4 kV
Class II
IEC 61010-1
Conformity IEC 61557-12 Edition 1 (08/2007)
Specification values
Standard multifunction meter
Other complementary
characteristics
-
SD
K55
-
0,5
-
-
-
-
-
37