Mounting the limit switches
Disconnect the device from the supply
voltage.
Remove the screws from the limit switch S2 and S1.
Mount the limit switch kit (1) on S1 and S2 as
shown.
Tighten with the new, longer screws.
Mount the additional switching cams (2) as well as
the spacer rings.
Setting the limit switch position
Reconnect to the supply voltage.
The switching cams can be adjusted with a screw-
driver size 2.
An instrument (e.g. ohm meter) must be used
for setting the switching position.
Move the actuator to the two end positions and set
the respective switching points.
Connect limit switches (disconnect the device from
the supply voltage).
Close the actuator with the housing cover and
connect to the supply voltage.
¥ ‡
!
V
81